Cooling Capacity - Sanyo CMH1972A Technical & Service Manual

Dc inverter multi-system air conditioner
Hide thumbs Also See for CMH1972A:
Table of Contents

Advertisement

5-2. Cooling Capacity

Outdoor Unit : CMH1972A
Indoor Unit
: KMHS0972
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY:
INDOOR
ENT. TEMP. °F (°C)
W.B.
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
NOTE
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.
2.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
×
3
19,100 BTU/h
D.B.
65
(18.3)
TC
19,180
72 (22.2)
SHC
17,130
76 (24.4)
SHC
19,180
80 (26.7)
SHC
19,180
84 (28.9)
SHC
19,180
88 (31.1)
SHC
19,180
TC
20,150
72 (22.2)
SHC
14,040
76 (24.4)
SHC
16,960
80 (26.7)
SHC
20,040
84 (28.9)
SHC
20,150
88 (31.1)
SHC
20,150
TC
21,140
72 (22.2)
SHC
10,610
76 (24.4)
SHC
13,700
80 (26.7)
SHC
16,790
84 (28.9)
SHC
19,700
88 (31.1)
SHC
21,140
TC
22,130
72 (22.2)
SHC
7,190
76 (24.4)
SHC
10,100
80 (26.7)
SHC
13,360
84 (28.9)
SHC
16,270
88 (31.1)
SHC
19,190
TC
23,020
76 (24.4)
SHC
6,840
80 (26.7)
SHC
9,930
84 (28.9)
SHC
12,840
88 (31.1)
SHC
15,930
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.
AIR FLOW RATE:
OUTDOOR
AMBIENT TEMP. °F (°C)
75
85
95
(23.9)
(29.4)
(35.0)
18,500
17,770
17,210
16,960
16,610
16,270
18,500
17,770
17,210
18,500
17,770
17,210
18,500
17,770
17,210
18,500
17,770
17,210
19,450
18,700
18,140
13,700
13,360
13,190
16,610
16,270
16,100
19,450
18,700
18,140
19,450
18,700
18,140
19,450
18,700
18,140
20,420
19,640
# 19,100
10,440
10,100
9,930
13,360
13,010
12,840
16,440
16,270
15,930
19,530
19,190
19,010
20,420
19,640
19,100
21,400
20,600
20,080
7,010
6,670
6,500
9,930
9,590
9,410
13,010
12,840
12,670
16,100
15,760
15,590
19,010
18,670
18,500
22,270
21,450
20,980
6,670
6,330
6,160
9,760
9,410
9,240
12,670
12,500
12,330
15,590
15,410
15,240
47
883 CFM
105
115
(40.6)
(46.1)
16,350
15,440
15,930
15,440
16,350
15,440
16,350
15,440
16,350
15,440
16,350
15,440
17,250
16,290
12,840
12,330
15,760
15,410
17,250
16,290
17,250
16,290
17,250
16,290
18,180
17,180
9,590
9,240
12,500
12,160
15,760
15,240
18,180
17,180
18,180
17,180
19,130
18,100
6,160
5,810
9,240
8,900
12,330
11,990
15,240
14,900
18,330
17,990
20,000
18,930
5,980
5,640
9,070
8,730
11,990
11,640
14,900
14,730

Hide quick links: