7. High altitude setting
1. Simultaneously turn selector dials
"
" and "
tr
" to their center
position. "SERV" appears in the
display. (To do the following step,
"SERV" must still be shown in the
display.)
2. Turn selector dial "
tr"
all the way to the "q q q q Reset" position.
3. "
appears on display along with
r"
" i i i i "
flashing set value
or
4. With selector dial"
", set the value
to "2 2 2 2 " for operation above 5,000' /
1,500 m.
Turn the selector dial "
center position to the right or left, as
shown in Fig. 54.
Value
Operation
i
Altitude < 5,000' / 1,500 m
2
Altitude > 5,000' / 1,500 m
5. Do not adjust the selector dials for
at least 15 seconds. The set value
" i i i i "
"2 2 2 2 "
or
is then saved and the
control unit returns to standard
mode.
6. Turn ON/ /OFF switch OFF and then
ON. When completed, it will activate
the designated setting
Note:
When the boiler is initially turned on, a
self-diagnostic check is initiated. Wait
until the temperature display is
stabilized and the boiler's actual
temperature is displayed.