Table Of Contents - Weil-McLain UltraOil 2 Series Manual

Series 2, oil-fired water boiler

Advertisement

'llltlta()lt.
Series 2
WATER BOILER -
Boiler Manual
Ratings
~UDI
........
CERTIFIEDTM
~
~
c
us
c
Boiler
AHRI
DOE
CSA
CSA
Model
Burner
Heating
Input
Output
Number
Capacity
Capacity
GPH#20il
MBH
MBH
Btuh
Notes:
Notes
1,
6
Notes 2,
6
Note2
0.80
98
112
98
1.00
122
140
122
1.0 GPH
1.20
146
168
146
1.40
172
196
172
Notes:
(
1) Based on
standard
test procedures prescribed by
the
United States Department
of Energy
at combustion
condition of 13.0%
C02
and -0.02"
w.c.
breeching
draft.
(2)
Ratings
shown
are
for sea
level applications
only.
For
altitudes above 2,000 feet, derate the product
capacity by 4o/o per 1,000 feet above
sea
level.
(3)
Net AHRI ratings are based on net installed
radiation
of
sufficient quantity for the requirements
of
the building and nothing need be added for
Part
number
550-141-987/0912
Net
AHRI
Ratings
MBH
Notes3,6
85
106
127
150
H
Boiler
Shipping
DOE
Flue
Draft
Water
Weight,
Seasonal
Conn.
Loss
Content
Approx.
Efficiency
Size
Through
Boiler
Gallons
Pounds
AFUE
o/o
Inches
w.c.
Note4
NoteS
15.0
636
86.5
6"
0.000
15.0
636
86.5
6"
0.020
18.3
737
86.2
6"
0.025
21.5
852
86.5
6"
0.040
normal piping and pick-up. Water ratings are based
on
a piping and pick-up allowance of 1.15.
An
additional
allowance
should
be made for unusual piping and pick-
up loads.
Consult
local
Weil-McLain Sales
Office.
(
4) See page 12 for minimum breeching and chimney
sizing.
( 5)
Boiler draft losses
are
based on operation
at
lllf2o/o
C0
2
Set breeching draft at -0.02 inch water
column.
(
6) MBH refers to thousands of Btu per hour.
39