'llltlta()lt.
Series 2
WATER BOILER -
Boiler Manual
Connect water piping
(continued)
DIAPHRAGM
expansion
tank
(Figure 6)
Make sure expansion tank size will
handle
boiler and
system water volume and
temperature.
Tank
must
be
located
near boiler before inlet to circulator.
See
tank manufacturer's instructions for details.
lA
CAUTlON
I
Undersized expansion
tanks cause
system
water
to be
lost from
relief
valve and
makeup water added through
fill
valve.
Eventual
section failure
can result.
CLOSED
expansion
tank
(Figure
7)
Ensure
expansion tank size will
handle
boiler and
system water volume
and
temperature.
lA
CAUTlON
I
Undersized expansion
tanks cause
system
water
to be
lost from
relief
valve and
makeup water added through
fill
valve.
Eventual
section failure
can result.
Pitch
any
horizontal
piping up towards tank
1 inch
per
5 feet of
piping.
Part number 550-141-987/0912
Figure 6
Supply
Figure 7
Near-boiler
piping,
with diaphragm
expansion tank
(!)outlet
@Return
®Relief
valve
@
Pfpe to drain
@
Drain valve
@
Isolation valves
®
Boiler circulator
®Diaphragm-type
expansion tank
®Air
separator and
auto air vent
· -
By
others
• -
Supplied with
boiler
Near-boiler
piping, with closed expansion tank
(!)Outlet
@Return
®Relief
valve
@
Pipe to drain
@
Drain
valve
@
Isolation valves
®
Soller circulator
@Ciosed·type
expansion tank
®Air
separator
·
-By
others
· -
Supplied with
boiler
15