Troubleshooting - Honeywell TH5110D Installation Instructions Manual

Non-programmable thermostat
Hide thumbs Also See for TH5110D:
Table of Contents

Advertisement

TROUBLESHOOTING

Symptom
Display is blank.
Temperature settings do
not change.
Heat does not turn on
(Heat On is solid in the
display).
Cooling does not turn on
(Cool On is solid in the
display).
Fan does not turn on in a
call for heat (electric
furnace).
Heat pump puts out cool
air in the heat mode and
warm air in the cool
mode.
Both the heating and
cooling equipment are
running at the same
time.
Table 5. Troubleshooting
Possible Cause
Thermostat is not powered.
The highest or lowest temperature
setting was reached.
Heating equipment failure.
Loose or broken wire connection
between thermostat and heating
equipment.
Cooling equipment failure.
Loose or broken wire connection
between thermostat and cooling
equipment.
Fan Control in Heating (Installer Setup
Number 3) is set to Gas or Oil Furnace
(Setting 0).
Changeover Valve (Installer Setup
Number 2) is not configured to match the
changeover required by the installed
heat pump.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 1) is set to Heat Pump
(Setting 1).
Heating and cooling wires are shorted
together.
TH5110D NON-PROGRAMMABLE THERMOSTAT
Check for 24 Vac between Rc and C.
Check that fresh AAA alkaline batteries are
installed as marked on the battery holder.
Temperature setting range:
Heating: 40° F to 90 °F (4.5 °C to 32 °C)
Cooling: 50° F to 99°F (10°C to 37°C)
Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the heating equipment to
find the cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the heating equipment to find the cause of
the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is
not present, check wire connection (loose or
broken) between the thermostat and the
heating equipment.
Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the cooling equipment to find
the cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the cooling equipment to find the cause of
the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is
not present, check the wire connection
(loose or broken) between the thermostat
and the cooling equipment.
Set Fan Control in Heating (Installer Setup
Number 3) to Electric Furnace (Setting 1).
Set Changeover Valve (Installer Setup
Number 2) to match the changeover
required by the installed heat pump.
Set System Type (Installer Setup Number 1)
to match the installed heating and/or cooling
equipment.
Separate the shorted heating and cooling
wires.
11
Action
69-1712—1