Integration - Honeywell TB7600 Integration Manual

Tb7600 series bacnet thermostats
Table of Contents

Advertisement

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS

INTEGRATION

This section provides compatibility and programming information useful when setting up TB7600 Series thermostats on a WEBs-
AX building automation system.
Global Commands
The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front-end.
GLOBAL COMMANDS ALL DEVICES
(ALL THERMOSTATS)
OUTDOOR TEMPERATURE AND HVAC PLANT CURRENT MODE
GLOBAL COMMANDS SPECIFIC DEVICES
(SPECIFIC AREA THERMOSTATS)
SCHEDULE AND OUTDOOR TEMPERATURE
ROOM TEMPERATURE FOR TESTING AND OVERRIDE
GLOBAL COMMAND CONTROL LEVEL
Fig. 6. Global commands from a BAS front-end to a TB7600 series thermostat.
63-4523—02
OUTDOOR TEMPERATURE
BAS CURRENT ENERGY SAVINGS MODE
SCHEDULE
RESTRICT SER ACCESS TO THERMOSTAT
BAS FRONT-END
OUTDOOR TEMPERATURE (AV9)
SYSTEM MODE (MV13)
FAN MODE (MV15)
OCCUPANCY COMMAND (MV12)
OCCUPIED HEATING SETPOINT (AV42)
UNOCCUPIED HEATING SETPOINT (AV44)
OCCUPIED COOLING SETPOINT (AV43)
UNOCCUPIED COOLING SETPOINT (AV45)
KEYPAD LOCKOUT (MV18)
ROOM TEMPERATURE (AV7)
MSTP NETWORK
8
TB7600 SERIES TSTAT
DEVICE LEVEL
M32570