BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
Standard Object Types Supported
Supported
Object Type
Analog Input
Analog Value
Binary Input
Binary Value
Device
Group
Multi-state Value
Schedule
a
The following AV's are defined as read only. When Out_of_Service properties is set to true, the Present_Value if written is not
derived from the application level of the thermostat.
• Room Humidity (AV11)
• PI Heating Demand (AV20)
• PI Cooling Demand (AV21)
• Economizer Output (AV22)
• Eff Reset Humidification RH Spt (AV96)
• Humidifier Output (AV101)
b
Object_Name property is writable for 1 object only :
• Room_Temperature (AV7)
Proprietary Properties
Property name
Major_Version
MS/TP_Address
MS/TP_Baud_Rate
Sensor_Offset
63-4523—02
Table 6. Standard Object Types Supported
Dynamically
Objects
Creatable
Table 7. Proprietary Properties
ID
BACnet Data type
1000
CharacterString
1001
Unsigned
1002
Unsigned
1005
REAL
Optional
Dynamically
Properties
Deletable
Supported
Reliability
Reliability
Reliability
Active_Text
Inactive_Text
Reliability
Active_Text
Inactive_Text
Max_Master
Max_Info_frames
Reliability
States_Text
Weekly_schedule
Description
The version number of the BACnet communications
module. This is the hardware version number.
Display the MAC layer address of the module
Display the communication baud rate of the module
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.
18
Writable Properties
Out_of_Service
Present_Value
Out_of_Service
Object_Name
Out_of_Service
Present_Value
Out_of_Service
Object_Identifier
Object_name
Max_Master
N/A
N/A
Present_Value
Out_of_Service
Present_Value
Weekly_Schedule
a
a
b

Advertisement