Step 6 - Configure The Fire Panel; Step 7 - Test The System; Ipgsm-Com Trouble Detection Information - Honeywell 800-04433V1 Installation And Setup Manual

Commercial fire communicator
Table of Contents

Advertisement

iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide
STEP 6 – Configure the Fire Panel
1. Ensure the Telco Fault on the panel is enabled. Then choose a setting that is no higher than 90
seconds (or as close to that) as the panel allows.
2. Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string
(usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds
after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think
the phone number is complete and cause it to generate the high-low tones at an incorrect moment.
STEP 7 – Test the System
1. Close the Wall Outlet Box, then close and lock the cabinet cover.
2. Refer to the fire panel's installation/operation guide the testing procedure.
3. (Notify the monitoring station that a test will be conducted.) Test the system to ensure it is
operating.

iPGSM-COM Trouble Detection Information

Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM-COM, and Telco 2 is used by
the iPGSM-COM to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use
Telco 2 to report events if there are no faults in the iGSM Communications module.
Fault Condition
PowerBoost1 fault
iGSM Communications Module fault
Failure of one of the two
communications paths.
Failure of both communications
paths.
Dialer Capture Module buffer is full.
Indication to Fire Panel
Telco 2 is cut.
Telco 2 is cut.
Telco 1 and 2 are cut.
Hang up. (Panel will retry, giving the buffer a chance to empty.)
– 7 –

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ipgsm-com

Table of Contents