LRM2070, LRM2080, LRM2090 Datasheet
OccuSwitch DALI sensor/controller
Settings done by IR remote.
The following settings are sent all at once with the green SEND button.
After selection of the function the red LED on the transmitter will
switch on.

Change IR group

Both the OccuSwitch DALI and transmitters can operate in 7 different
groups. Both the transmitter and OccuSwitch DALI must be in the same
IR group.
Select "group A-G" followed by the desired IR group (A-G, buttons
1 to 7).

Change power-up behavior

The OccuSwitch DALI switches the output on when it is connected to
the mains. If the area is vacated, the lights will switch off after 5 minutes.
It is possible to leave the output off and start movement detection
30 seconds after the mains is connected.
Select "power up ON/OFF" followed by either "on" or "off ".

Restore defaults

To restore the default settings, aim the IRT9090 towards the
OccuSwitch DALI and press on "reset" and press SEND.
Attention
The IRT9090 will transmit all parameters when the SEND
button is pressed.

Error states

The OccuSwitch DALI is designed to create (if possible) a safe situation
if the device itself or its peripherals fail.
Depending on the failure the OccuSwitch DALI will continue "as good
as possible" or switch the lights on.
The LED on the device will be always yellow and will not switch off,
even if there is no movement or communication detected.
Please refer to the manual of the OccuSwitch DALI for more
information and diagnostic flow charts.
Attention
The OccuSwitch DALI should not be used in the following
situations:
• I n applications outside the specification range, most notabley heights
above 4 meter.
• E nvironmental conditions other than in a normal office environment
(temperature, humidity).
• I n applications with heat sources like electrical heaters, within the
detection range of the device.
• I n applications with (semi-continuous) IR appliances like IRDA
communication, IR communication between PDA and phones and
other devices, headsets operating with IR communication, etc.
Please note that some devices with IR communication send IR
messages, even when there is no active communication link. These
features must be disabled.
• I n applications with electronic drivers that operate up or near
a frequency of 36Khz. Also when these drivers are not used in
combination with the device, but the light from the lamps they
operate is visible to the IR receiver.
LED
Flash Red, Yellow or Green
Circulation (long/short)
Yellow/Green
Red/Green
Green/Red
Continuously
Green (when lights are on)
Yellow
Red
Fast sequence
Red/Yellow/Green
10/15
Movement or communication
detected.
Red = 100 – 70%
Yellow = 70 – 40%
Green = 40% - off
Auto commissioning with current
light level
Auto commissioning
DALI commissioning in progress
In 100 hours burn in mode
(no dimming possible)
Internal error
Short circuit on DALI channel
Trigger received from parallel unit
(LRM2080 only)