LRM2070, LRM2080, LRM2090 Datasheet
OccuSwitch DALI sensor/controller
LCC2070
LCC2080
cable set
cable set
L N
L N
7-pole
STELVIO
plug MRT3
P 5,08/07
500
V01 VE
Dimensions in mm
80
95
52 mm
2 inch
7-pole
STELVIO
plug MRT3
P 5,08/07
V01 VE
40 mm
60 mm
Ø 95 mm

General description

The OccuSwitch DALI is a combined sensor and controller. It will dim
and switch on the lights in a room or area on occupancy and available
daylight, with options for local override, parallel operation and network
links to Building Management Systems (BMS).
Savings of up to 75% can be achieved with functions like daylight
depending dimming, occupancy control and over dimension correction.
The OccuSwitch DALI is designed for an office area of 20 to 25 m
or a classroom of around 40 m
tripled, with the extension sensor LRM8118. Up to 15 drivers (usually
luminaires) can be controlled.
A detachable wiring connector enables easy installation and mounting
in the ceiling. Separate Wieland cables are available for an even easier,
faster, trouble-free installation.
It is possible to link up to 22 (advanced only) OccuSwitch DALI units in
parallel to cover larger areas with a specific "open plan" mode to ensure
maximum comfort and savings.
The LRM2090 can be linked to most BMS or other control systems that
have standard DALI interfaces (up to 64). This makes simple yet very
effective control scenarios possible in a building.
The OccuSwitch DALI family exists of:
LRM2070
Basic functionality
LRM2080
Parallel operation
LRM2090
DALI interface for BMS or other network
LCC2070
Wieland cable for LRM2070
LCC2080
Wieland cable for LRM2080 and LRM2090
LRH2070
Ceiling mounting box
LCU2070
Push-Button Unit for 4 switches
IRT9090
Extended IR programming tool
2
but the area can be doubled, or even
1/15
,
2

Advertisement

Table of Contents
loading

Summary of Contents for Philips OccuSwitch DALI LRM2070

  • Page 1 LRM2070, LRM2080, LRM2090 Datasheet 1/15 OccuSwitch DALI sensor/controller General description The OccuSwitch DALI is a combined sensor and controller. It will dim and switch on the lights in a room or area on occupancy and available daylight, with options for local override, parallel operation and network links to Building Management Systems (BMS).
  • Page 2 LRM2070, LRM2080, LRM2090 Datasheet 2/15 OccuSwitch DALI sensor/controller Applications Typical applications The OccuSwitch DALI is designed for use in offices and similar applications like schools, including corridors, meeting rooms, etc. It is optimized for recessed ceiling mounting and for mounting heights between 2.5 and 4 meter.
  • Page 3 The OccuSwitch DALI can be used with one channel only or two With the IRT9090 the walk test mode can be started. This makes it (window / corridor control), using the physical outputs (LRM2070 only). possible to check if the OccuSwitch DALI and the connected luminaires However all versions can be used with DALI addressing as well.
  • Page 4 4 switches to the OccuSwitch DALI, to dim and switch different DALI groups. This PBU is connected to the DALI channel DA and/ or X for LRM2070 or DA only for LRM2080 and LRM2090. It derives its power form the DALI channel, so no additional power supply is required.
  • Page 5 A query on the ACTUAL LEVEL will result in the average value of the DALI <-> DyNet window and corridor side. Philips Dynalite DDBC120-DALI-DyNet with 1 DALI channel The OccuSwitch DALI performs a regular scan on the connected drivers. Queries on status and lamp failure will report the result of this The Loytec gateways need separate DALI power supplies.
  • Page 6 LRM2070, LRM2080, LRM2090 Datasheet 6/15 OccuSwitch DALI sensor/controller Addressing Energy calculator (Loytec gateways only) The OccuSwitch DALI supports the standard ways to address units. The gateway and OSD work together to form a beautiful energy All address (including grouping) related commands are NOT relayed to calculation function.
  • Page 7 LRM2070, LRM2080, LRM2090 Datasheet 7/15 OccuSwitch DALI sensor/controller Mechanical installation The OccuSwitch DALI can be mounted in two ways; recessed in the ceiling or surface-mounted using the ceiling box. The ceiling box (LRH2070) has a breakout port for cable ducts and a breakout centerpiece.
  • Page 8 LRM2070, LRM2080, LRM2090 Datasheet 8/15 OccuSwitch DALI sensor/controller Electrical installation The OccuSwitch DALI can be installed with either conventional wiring The DALI signal from a driver or luminaire, although low voltage and or Wieland connectors. For the second option, the Wieland cable isolated from mains, cannot be treated as a safe signal (SELV).
  • Page 9 LRM2070, LRM2080, LRM2090 Datasheet 9/15 OccuSwitch DALI sensor/controller Commissioning Desired standard light level There are three ways to set the light level. Automated mode Manual with normal control Manual with IRT9090 Step 1 Press the OccuSwitch DALI button Step 1 Use a remote or switch to set the...
  • Page 10 LRM2070, LRM2080, LRM2090 Datasheet 10/15 OccuSwitch DALI sensor/controller Settings done by IR remote. The following settings are sent all at once with the green SEND button. Flash Red, Yellow or Green Movement or communication After selection of the function the red LED on the transmitter will detected.
  • Page 11 Comfort mode, always light This mode works differently for the advanced (LRM2080) and network (LRM2090) OSD when compared with OSD basic (LRM2070). For LRM2080 & LRM2090 the lights will switch off (the basic never switches off) when none of the advanced OccuSwitch DALI units in the parallel network detect movement. If one or more do detect...
  • Page 12 LRM2070, LRM2080, LRM2090 Datasheet 12/15 OccuSwitch DALI sensor/controller...
  • Page 13 Short circuit and protection The DA (all units) and X (LRM2070 and LRM2080) interface provides DALI (or other) power in order to be able to communicate. These interfaces are protected against a short circuit if used within specification.
  • Page 14 LRM2070, LRM2080, LRM2090 Datasheet 14/15 OccuSwitch DALI sensor/controller Technical data Environmental conditions Protection Interface is short-circuit proof Storage conditions Transmission rate Max. 1200 bits per second Temperature -25 ºC to +85ºC DALI voltage 11.5VDC to 21.5VDC Relative humidity 10% to 95 %; no condensation Connector type Wieland BST 14i2;...
  • Page 15 LRM2070, LRM2080, LRM2090 Datasheet 15/15 OccuSwitch DALI sensor/controller Packing data Type Dimensions Material Weight (Kg) (mm) gross LRM2070 105 x 95 x 58 cardboard 0.12 0.15 LRM2080 105 x 95 x 58 cardboard 0.12 0.15 LRM2090 105 x 95 x 58 cardboard 0.12...