Refrigeration Cycle Diagram - LG LBNG3061YL Service Manual

Ceiling duct air conditioner
Table of Contents

Advertisement

Refrigeration Cycle Diagram

• LB-G3061YL
INDOOR UNIT
LIQUID PIPE
SENSOR
HEAT
EXCHANGER
Pipe size(Diameter: ø)
MODEL
LB-G3061YL
• Rated performance for refrigerant line length of: 7.5m
• If it is installed at a distance of 15m, 300g of refrigerant should be added (15-7.5) x 40g = 300g
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LIQUID SIDE
INDOOR
TEMPERATURE
SENSOR
GAS SIDE
Gas
Liquid
5/8"
1/4"
OUTDOOR UNIT
LEV
GAS PIPE
SENSOR
COMPRESSOR
Piping length(m)
Rated
Max.
7.5
15
- 8 -
HEAT
EXCHANGER
REVERSING
VALVE
DISCHARGE
PIPE SENSOR
COOLING
HEATING
*Additional
Elevation(m)
refrigerant
Rated
Max.
7.5
12.5
LGE Internal Use Only
HEATING
SENSOR
(g/m)
40