Heat Controller, Inc.
8.3.1. Compressor checking (Model: DA150S1C-20FZ)
Measure the resistance value of each winding by using the multi-meter.
Outdoor Fan Motor (Model: YDK53-6FB)
Measure the resistance value of each winding by using the multi-meter.
Outdoor Fan Motor (Model: YDK53-6NB)
Measure the resistance value of each winding by using the multi-meter.
VMH SerieS
Position
Blue - Red
Blue - Black
Red - Blue
Position
Black - Red
Red -Yellow
Position
Black - Red
Red -Yellow
43
42
Resistance
Value
0.95Ω
(20℃)
Resistance
Value
56Ω (20℃)
76Ω (20℃)
Resistance
Value
56.5Ω (20℃)
117.5Ω (20℃)
Service Manual