8.4.3.5 High evaporator coil temp.T2 protection:
(1) T2>TEH2 compressor running frequency decreases to the lower level every 20s. If the frequency
decreased to F2 and the T2 still over TEH2 for 3 minutes, the compressor will stop. If T2 deceased to lower
than 118°F/48°C, or 118°F/48°C <T2< TEH2 last for 6 minutes, release the frequency limit control.
(2) If T2>140°F/0°C, the compressor stops and restarts when T2<118°F/48°C
8.4.4 Auto-mode
This mode can be selected by the remote control and the set temperature can be changed between
17~86°F/62°C.
In auto mode, the machine will select cooling, heating or fan-only mode according to the difference
between T1 and Ts.
T1-Ts
T1-Ts>1°F
-1< T1-Ts ≤1°F
T1-Ts ≤-1°F
Indoor fan will run in auto fan of the relevant mode.
The louver operates the same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will stop for 15 minutes and
then choose mode according to T1-Ts again.
If the set temperature is modified, the unit will choose run function again.
VMH SerieS
Unit
°F
9K/12K
127°F 53°C
18K /24K
131°F 55°C
Running mode
Cooling
Fan-only
Heating
30
31
(°C)
TEH2
Service Manual