Check Inlet Gas Supply - Lochinvar Shield SNR150-100 Installation & Service Manual

Commercial
Hide thumbs Also See for Shield SNR150-100:
Table of Contents

Advertisement

6
Gas connections
Table 6A Natural Gas Pipe Size Chart
Nominal
Iron Pipe
Size (Inches)
10
20
1/2
175
120
3/4
369
256
1
697
477
1-1/4
1400
974
1-1/2
2150
1500
2
4100
2820
2-1/2
6460
4460
3
11200
7900
4
23500 16100 13100 11100 10000
Shield water heaters are typically shipped ready to fire on natural gas. Check the water heater rating plate to
WARNING
determine which fuel the water heater is set for. In order to operate on LP gas contact the factory, an orifice
MUST BE installed or a gas valve adjustment MUST BE made. Failure to comply could result in severe
personal injury, death, or substantial property damage.

Check inlet gas supply

CSA or UL listed flexible gas connections
NOTICE
are acceptable, but you must exercise
caution to ensure that the line has adequate
capacity to allow your water heater to fire
at full rate. Consult with local codes for
proper installation or service procedures.
DO NOT adjust or attempt to measure
WARNING
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas
and propane (when configured for LP),
requiring no field adjustment. Attempting
to alter or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death, or substantial property
damage.
The gas piping must be sized for the proper flow and length
of pipe, to avoid excessive pressure drop. Both the gas meter
and the gas regulator must be properly sized for the total gas
load.
If you experience a pressure drop greater than 1 inch w.c.,
the meter, regulator, or gas line is undersized or in need of
service. Perform the steps below when checking inlet gas
supply:
1.
Disconnect power from the appliance.
2.
Shut off gas to the appliance.
3.
Loosen the set screw one (1) full turn from inside the
pressure tap on top of the gas valve. Place the tubing of
the manometer over the tap once the set screw is
loosened as shown in FIG.'s 6-4 thru 6-6.
4.
Slowly turn on the gas supply at the field installed
manual gas valve.
(continued)
Natural Gas Pipe Capacity Chart
Length of Pipe in Straight Feet for 1/2 PSI
30
40
50
60
97
82
N/A
N/A
205
174
155
141
384
328
292
267
789
677
595
543
1210
1020
923
830
2260
1950
1720
1560
3610
3100
2720
2460
6400
5400
4870
4410
9000
TM
70
80
90
100
N/A
N/A
N/A
N/A
128
121
113
106
246
236
210
200
502
472
441
410
769
707
666
636
1440
1330
1250
1180
2310
2100
2000
1900
4000
3800
3540
3330
8300
7690
7380
6870
5.
Reconnect power to the appliance.
6.
Adjust the temperature set point on the control panel of
the electronic control module to call for heat.
7.
Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the control panel.
8.
Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.
9.
If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.
10. If the gas pressure is out of range, contact the gas utility,
gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.
11. Disconnect power from the appliance.
12. Shut off the gas to the appliance.
13. Remove the manometer from the pressure tap on top of
the gas valve. Re-tighten the set screw inside the pressure
tap.
When re-tightening the set screw, be sure to
WARNING
tighten securely to prevent gas leaks.
Do not check for gas leaks with an open
flame -- use the bubble test.
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
14. Reconnect gas to the appliance.
15. Reconnect power to the appliance.
16. Adjust the temperature set point on the control panel of
the electronic control module to the desired water
temperature so the appliance will call for heat.
Installation & Service Manual
125
150
175
N/A
N/A
N/A
95
86
79
179
164
149
369
333
308
564
513
472
1100
974
871
1700
1540
1400
3000
2720
2500
6150
5640
5130
Failure to
200
N/A
74
138
287
441
820
1300
2340
4720
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents