Haier AD182ALERA Service Manual page 44

Commercial air conditioning
Table of Contents

Advertisement

11) Fault in drain system
confirm the malfunction
according to the fault code list
Is drain pipe clogged?
no
Is pump motor in
good condition?
yes
Is drain pan dirty and
float switch ineffective?
no
Is float switch holder tinted
that float can't move, or too
close to pump motor that
interference arises?
no
Check if float switch is in good
condition with multimeter
no
Replace indoor
PCB
Note: Float switch is close in normal state, when being activated, it is open.
Voltage between both ends is 0V when close, approximately 5V when open.
12) Phase loss or phase failure
confirm the malfunction
according to the fault code list
Check if the phase detecting
circuit is correct according to
ourdoor wiring diagram
yes
Is there phase loss
or phase failure?
no
Is fault corrected after
sequence of either two of three
RST phases is adjusted?
no
replace outdoor
PCB
Commercial Air Conditioner
yes
Unclog pipe and
water pump
yes
Replace water
pump
yes
Clean drain pan
yes
Adjust holder
yes
Replace float
switch
if the failure disappear
no
after correcting the
wiring
no
adjust power
supply
Model: AD182ALERA AD362AHERA
no
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad362ahera

Table of Contents