BREAK-IN PROCEDURE/DAILY OPERATION
BREAK-IN PROCEDURE
After the generator has been started, check for proper opera-
tion and then encourage a fast wann-up. Run the generator
between 20% to 60% of full load for the fIrst 10 hours.
A
CAUTION:
00 not attempt to break-in your genera-
tor by running without
a
load.
After the fIrst 10 hours of the generators' operation, the load
can be increased to the full-load rated output; then periodi-
cally vary the load.
Avoid overload at all times. An overload is signaled by a
smoky exhaust with reduced output voltage and frequency.
Monitor the current being drawn from the generator and keep
it within the generators' rating. Since the generator operates
at 3600 rpm to produce 60 hertz, or at 3000 to produce 50
hertz, control of the generator's engine break-in is governed
by the current drawn from the generator.
To protect against unintentional overloading of the generator,
the generator's output leads should be routed through a cir-
cuit breaker that is rated at the rated output of the generator.
NOTE:
Be aware of motor starting loads and the high
current drawn required for starting motors. This starting
amperage drawn can be
3
to
5
times normal running amper-
age. See GENERATOR INFORMATION in this manual.
CHECK LIST
Follow this checklist each day before starting your generator.
• Record the hourmeter reading in your log (engine hours
relate to the maintenance schedule).
• Visually inspect the engil!e for fuel, oil, or water leaks.
• Check the oil level (dipstick).
• Check the coolant level in the coolant recovery tank.
• Check your fuel supply.
• Check the starting batteries (weekly).
• Check the drive belt for wear and proper tension (weekly).
• Check for abnormal noise such as knocking, vibration and
blow-back sounds.
• Confmn exhaust smoke:
When the engine is cold - White Smoke.
When the engine is wann - almost Smokeless.
When the engine is overloaded - some Black Smoke.
NOTE:
Some unstable running may occur in a cold engine.
This condition should abate as normal operating temperature
is reached and loads are applied.
A
CAUTION:
00 not operate the generator for long
periods of time without
a
load being placed on the
generator.
STOPPING THE GENERATOR
Remove the major AC loads from the generator one at a time.
Allow the generator to run for a few minutes to stabilize the
operating temperature and press the STOP switch down, (see
CONTROL PANELS).
NOTE:
After the first
50
hours of generator operation check
the maintenance schedule for the
50
hour service check.
GENERATOR ADJUSTMENTS
Once the generator has been placed in operation, there may
be governor adjustments required for engine speed (hertz)
during the engine's break-in period (fIrst 50 hours) or after
this period (see ENGINE SPEED (HER1Z) ADJUSTMENT
under ENGINE ADJUSTMENTS. A no-load voltage adjust-
ment may also be required in conjunction with the engine's
speed adjustment (see GENERATIOR INFORMATION).