Sidewalls/Surrounds; Frame The Fireplace - Heat & Glo Wood Burning Fireplace RH-36 Series Owner's Manual

Wood burning fireplace installation and operation
Hide thumbs Also See for Wood Burning Fireplace RH-36 Series:
Table of Contents

Advertisement

C. Sidewalls/Surrounds
Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fi replace opening.
Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area,
Figure 6.3.
FLUSH
FRONT
11 1/4 in.
[286 mm]
[305 mm]
Figure 6.3
Mantel Leg or Wall Projections (Acceptable on both sides of opening)
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.
Framing across the top of fi replace must be above top standoffs.
2 in. (51 mm)
min. air space
clearance
from chimney.
C
B
Figure 6.4
Framing the Fireplace
20
A
B
12 in.
Note: Framing must be
extended straight up,
all the way to the ceiling.
Header MUST NOT be notched!
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
D
A
Heat & Glo • RH-36/RH-42 • 4044-153 • Rev W • 11/08
4 in.
BRICK
[102 mm]
FRONT
9 3/4 in.
[248 mm]
12 in.
[305 mm]
Model
RH-36
RH-42
* If interior of chase will be drywalled, add the thickness to
this measurement.
** Adjust header height for a raised fl oor under fi replace.
A
Fireplace
Model #
Opening
in.
36
RH-36
mm
914
in.
42
RH-42
mm
1067
A
B*
C**
in.
42
21 1/2
39 3/4
mm
1067
546
1010
in.
48
21 1/2
39 3/4
mm
1219
546
1010
B
Outside Di-
mensions
41
1041
47
1194
D
8
203
8
203

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rh-42 series

Table of Contents