C. Sidewalls/Surrounds
Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.
Combustible and non-combustible mantel legs, surrounds and stub walls may be constructed within the gridded area,
Figure 6.3.
FLUSH
FRONT
11 1/4 in.
[286 mm]
[305 mm]
Figure 6.3
Mantel Leg or Wall Projections (Acceptable on both sides of opening)
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.
Framing across the top of fireplace must be above top standoffs.
2 in. (51 mm)
min. air space
clearance
from chimney.
C
B
Figure 6.4
Framing the Fireplace
20
A
B
12 in.
A
Heat & Glo • RH-36/RH-42 • 4044-153 • Rev AC • 1/11
4 in.
BRICK
[102 mm]
FRONT
9 3/4 in.
[248 mm]
12 in.
Model #
[305 mm]
RH-36
RH-42
Header MUST NOT be notched!
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
D
Model
in.
RH-36
mm
in.
RH-42
mm
* If interior of chase will be drywalled, add the thickness to
** Adjust header height for a raised floor under fireplace.
A
Fireplace
Outside
Opening
Dimensions
in.
36
mm
914
in.
42
mm
1067
A
B*
C**
42
21 1/2
39 3/4
1067
546
1010
48
21 1/2
39 3/4
1219
546
1010
B
41
1041
47
1194
D
8
203
8
203