E. Combustible Mantel
See Figure 11.9.
A combustible mantel may be positioned no lower than 12
in. (305 mm) above the top of the fi replace opening.
A combustible mantel may have a maximum depth of
12 in. (305 mm).
Combustible trim and materials cannot be placed within
6 in. (152 mm) of the fi replace opening (top or sides).
Combustible materials projecting more than 1-1/2 in.
(38 mm) shall not be placed within 12 in. (305 mm) from
the top of the fi replace opening.
Combustible trim must not cover the metal surfaces of
the fi replace.
Mantel clearance is in accordance with Section 7-3.3.3
of ANSI/NFPA211.
Combustible Wall
Figure 11.9 Clearances to Mantels or other Combustibles above Fireplace
42
2 x 4 stud wall
12 in./305 mm MAXIMUM
Standoffs
Measured from top of fireplace opening
Heat & Glo • RH-36/RH-42 • 4044-153 • Rev W • 11/08
Combustible
Decorative Facing
Noncombustible
Decorative Facing
12 in./305 mm MINIMUM
Seal joint with
non-combustible
sealant
7 ft (2134 mm)
minimum
base of fireplace
to ceiling