C. Install the Termination Cap
Install the chimney sections up through the chase
enclosure. When using a TR11 Round Termination Cap,
the uppermost top section of pipe must extend 6 in.
(152 mm) above the top of the fl ashing collar to allow
installation of the storm collar and termination cap. See
Figure 6.5.
For installations utilizing a TR11T Round Telescoping
Termination Cap, the uppermost chimney section must
be below the top of the chase top, but not more than
14 -1/2 in. (368 mm) below the top of the chase top.
Minimum overlap of chimney and termination cap must
be 1-1/2 in. (38 mm). See Figure 6.6.
For installations utilizing an ST1175 Square Termination
Cap the last chimney section must not be more than
4-1/2 in. (114 mm) below the chase top. See Figure 6.7.
For installations utilizing an TCT1175 Terra Cotta Cap the
last chimney section must be between 7 in. (178 mm) below
the chase top and 2 in. (51 mm) above. See Figure 6.8.
For chase installations you can use a TR11 Round
Termination Cap, a TR11T Round Telescoping Termination
Cap, an ST1175 or a TCT1175 Terra Cotta Termination
Cap.
Install the termination cap following the instructions
provided with it.
Minimum 1-1/2 in. (38 mm) overlap of cap over pipe
6 in. (152mm) min.
Flashing Collar
Figure 6.5
Installing a TR11 Round Termination Cap
Flashing Collar
Top of Pipe
Figure 6.6
Installing a TR11T Round Telescoping Termination Cap
22
Storm Collar
2 in. (51 mm) min.
2 in. (51 mm) min. collar
Storm Collar
2 in. (51 mm) min.
14-1/2 in. (368mm) max.
1-1/2 in. (38 mm) min.
overlap
Heatilator • ST42A • 35038 Rev G • 02/05
Note: To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.
WARNING
Fire Risk
The minimum overlap of cap to pipe
MUST be met or chimney may separate
from cap.
Separation allows sparks, heat and embers
to escape.
Cap Standoff
1-1/2 in.
(38 mm) min.
overlap
Top of Pipe
Figure 6.7
Installing an ST1175 Square Termination Cap
1-1/2 in. (38 mm)
min. overlap
{
Top of Pipe
Figure 6.8
Installing a TCT1175 Terra Cotta Cap
Flashing Collar
2 in. (51 mm) min.
4-1/2 in.
(114 mm)
max.
The last section of pipe
must stop between the
distances given below.
2 in. (51 mm) above top
of the chase.
7 in. (178 mm) below top
of the chase.