C. Sidewalls/Surrounds
Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) (may be 24 in) from the fi replace
opening.
Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed per Figure 6.3.
Grid represents 1 in. scale
FLUSH
FRONT
10 3/4 in.
[273 mm]
12 in.
[305 mm]
Figure 6.3
Mantel Leg or Wall Projections (Acceptable on both sides of opening)
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
Observe all required air space clearances to combustible materials as shown in Figure 6.2.
Framing across the top of fi replace must be above top standoffs.
2 in. (51 mm)
min. air space
clearance
from chimney.
C
B
Figure 6.4
Framing the Fireplace
20
BRICK
FRONT
A
B
12 in.
[305 mm]
Note: Framing must be
extended straight up,
all the way to the ceiling.
D
A
* If interior of chase will be drywalled, add the thickness to this measurement.
** Adjust header height for a raised fl oor under fi replace.
Heat & Glo • EM-415, EM-485 • 33056 • Rev W • 10/08
Model #
in.
EM-415
mm
4 in.
[102 mm]
in.
EM-485
mm
9 3/4 in.
[248 mm]
Header MUST NOT be notched!
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
Model #
A
in.
43
EM-415
mm
1092
in.
49
EM-485
mm
1245
A
Fireplace Opening
Outside Dimensions
36
914
42
1067
B*
C**
23
41 1/2
584
1054
23
41 1/2
584
1054
B
42
1067
48
1219
D
8
203
8
203