Download Print this page

Installation - Honeywell C7061A Product Data

Dynamic self-check ultraviolet flame detector
Hide thumbs Also See for C7061A:

Advertisement

114465 Gasket, silicone rubber; for installing viewing
window (three required).
190971B Coil and Shutter Assembly.
C7061A:
114372 Quartz Viewing Window; rated for 20 psi (138 kPa).
120739 Gasket, fiber-neoprene; heat insulation and
seal-off for mounting flange.
C7061F:
122037 Quartz Viewing Window; rated for 100 psi
(690 kPa).
MOUNTING FLANGE
7-7/32
(183)
3-3/4
(95)
1/2–14 NPSM
2
LEADWIRES
C7061A1046: 1 INCH NPT
1
C7061A1038 AND C7061A1046: BRAD HARRISON® CONNECTOR.
2
Fig. 1. Dimensions of C7061A in in. (mm).
FACEPLATE
8
(203)
DIA.
1-
1/2
1/2-14 NPT
(38)
LEADWIRES
2 (51)
9 (229)
M 1 9 6 3
Fig. 2. Dimensions of C7061F in in. (mm).
Accessories:
C7061A:
122748 Quartz Viewing Window, rated for 50 psi
(345 kPa).
124204 Quartz Focusing Lens, rated for 20 psi (138 kPa);
increases the detector-sensed ultraviolet radiation.
123539 Antivibration Mount.
204341 Mirror Assembly.
124198 Mounting Flange, aluminum, with 1 inch NPT
internal threads for attaching to sight pipe.
190105 Water Jacket.

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
C7061A,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR
1
3/4–14 NPT
5-1/8 (130)
3-7/16
(87)
5-1/4 (133)
FACEPLATE
M10167A
1-11 1/2 NPT
PIPE
UNION
1 (25)
5
(127)
2-1/16
(52)
2
(51)
5/16-18 UNC-2B BY
3 (76)
7/16 (11) DEEP
MOUNTING HOLES (2)
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced flame safeguard
service technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Equipment damage hazard.
Sensing tube can fail to discriminate between
flame conditions.
Change sensing tube after 40,000 hours of continuous
use.
WARNING
Electrical shock hazard.
Can cause serious injury or death.
Disconnect power supply before beginning installation
to prevent electrical shock and equipment damage.
More than one disconnect may be involved.
IMPORTANT
1. Do not connect these detectors to non-Honeywell
manufactured controls (primaries, programmers,
multiburner systems, and burner management
systems). Unsafe conditions could result.
2. All wiring must be NEC Class 1 (line voltage).
3. Voltage and frequency of the power supply connected
to this detector must agree with the values marked on
the detector.
4. Sight the detector so it does not respond to ignition
spark.
5. On multiburner installations, each detector must
respond only to the flame of the burner it is
supervising.
6. Do not connect more than two C7061 Flame
Detectors in parallel.
Proper flame detector installation is the basis of a safe and
reliable flame safeguard installation. Refer also to the burner
manufacturer instructions. Carefully follow all instructions for
the best possible flame detection application.
Basic Requirements
The combustion flames of most carbon-based fuels emit
sufficient ultraviolet radiation to enable the C7061 Solid State
(Purple Peeper) Ultraviolet Flame Detector to prove the
presence of a flame in a combustion chamber. The detector is
mounted outside the combustion chamber with its mounting
flange or union threaded to one end of a sight pipe inserted
through the wall of the combustion chamber. The ultraviolet
sensing tube in the flame detector sights the flame through the
pipe.
When a flame is present, the UV tube in the C7061 senses the
ultraviolet radiation emitted. The C7061 then produces a signal
that is sent to the amplifier in the flame safeguard control. The
amplified signal pulls the flame relay into the control to allow
proper system operation.
Because it is necessary for the UV sensing tube to actually see
the flame, it is best to locate the detector as close to the flame
as physical arrangement, temperature, and other restrictions
permit. These restrictions are described in detail in the
following paragraphs.
3