Service And Maintenance Suggestions - Empire DV-55IP Installation Instructions And Owner's Manual

Fan type direct vent wall furnace
Table of Contents

Advertisement

Available languages

Available languages

SERVICE & MAINTENANCE SUGGESTIONS
GENERAL: All furnaces have been fire-tested to check for proper
operation. This includes, main burner flame, pilot flame, fan operation, fan
control, limit control and automatic valve operation. If the furnace fails to
function on initial installation, it is advisable to re-check the following:
1.
115 volts to the junction box.
2.
Inlet gas pressure.
3.
The 24 volt system.
4.
Type of gas being used and that shown on the rating label.
The Service Department at empire Comfort Systems, Inc. may be contacted
to assist in servicing furnace or call a qualified serviceman.
Servicing the Pilot and Main Burners, Pilot orifice, and Main Burner
orifices: Disconnect the gas supply at the inlet to the control valve. Then
remove the burner door to which the above components are attached.
Servicing The Fan Motor: The upper front panel, the shroud surrounding
the fan blade and fan blade must be removed.
Replacing Fan and Oiling the Motor
The fan motor should be cleaned and oiled once each heating season. To
reach the motor, withdraw the metal shroud surrounding the fan blade by
removing the screws on each side. Oil holes are located on the top at each
end of the motor. Use a few drops of #10 motor oil. To clean the motor,
blow air through its ventilation openings with a vacuum cleaner or low
pressure air source.
If fan motor is replaced, the silicone rubber gaskets, see Page 20, Index
No. 4, Part No. 712059, should also be replaced. The gaskets must be
stretched to fit the motor bolts into the gasket holes and then the motor
and gaskets installed on the motor mounting bars.
S 8 6 0 0 H
I N T E R M I T T E N T
SPECIFICATIONS
Lockout timing is 90 seconds. Ignition timing is until pilot lights or
lockout occurs.
Module shuts down and cuts power to gas control on flame failure. Gas
control closes to provide 100 percent lockout on flame failure. Manual
reset required.
ELECTRICAL RATINGS:
Voltage and frequency: 20.5 to 28.5V (24V nom.) 60 Hz.
Current rating: 0.2 A.
Valve contact ratings (at 24 Vac):
Run
Inrush
Pilot
1.0 a
10.0 a
Main 1.0 a
10.0 a
SPARK GENERATOR OUTPUT: 13kV peak at 25 pf load.
THERMOSTAT ANTICIPATOR SETTING: 0.2 A plus pilot valve rating
plus main valve rating.
THERMOSTAT COMPATIBILITY: Standard models compatible with all
open-close switch type 24 Vac thermostats capable of supplying rated
voltage and current to the module.
AMBIENT TEMPERATURE RATING: Minus 40 F to plus 175 F (minus
40 C to plus 79 C).
RELATIVE HUMIDITY RATING: 5 to 90 percent RH at 95 F.
FLAME FAILURE RESPONSE TIME: 0.8 seconds at 1.0 uA flame
current.
FLAME CURRENT: 1 uA, min.
CHeCKOUT
Check out the gas control system:
1. at initial installation of the appliance.
2. as part of regular maintenance procedures.
3. As the first step in troubleshooting.
12432-13-1008
I G N I T I O N
M O D U L E
4. any time work is done on the system.
STEP 1: Perform Visual Inspection.
a. With power off, make sure all wiring connections are clean and
tight.
B. Turn on power to appliance and ignition module.
C. Open manual shutoff valves in the gas line to the appliance.
D. Do gas leak test ahead of gas control if piping has been disturbed.
GaS LeaK TeST: Paint pipe joints with rich soap and water solution.
Bubbles indicate gas leak. Tighten joints to stop leak.
STEP 2:
Review Normal Operating Sequence and Module
Specifications.
STEP 3: Reset the Module.
a. Turn the thermostat to its lowest setting.
B. Wait one minute.
As you do Steps 4 and 5, watch for points where operation deviates
from normal. Refer to Troubleshooting Chart to correct problem.
STEP 4: Check Safety Lockout Operation.
a. Turn gas supply off.
B. Set thermostat above room temperature to call for heat.
C. Watch for spark at pilot burner.
D. Time length of spark operation. Maximum spark time is 90
seconds.
E. Open manual gas cock and make sure no gas is flowing to pilot or
main burner.
F. Set thermostat below room temperature and wait one minute before
continuing.
STEP 5: Check Normal Operation.
a. Set thermostat above room temperature to call for heat.
B. Make sure pilot lights smoothly when gas reaches the pilot burner.
C. Make sure main burner lights smoothly without flashback. Make
sure burner operates smoothly without floating or lifting.
D. If gas line has been disturbed, complete gas leak test.
GAS LEAK TEST: Paint gas control gasket edges and all pipe
connections downstream of gas control, including pilot tubing
connections, with rich soap and water solution. Bubbles indicate
gas leaks. Tighten joints and screws or replace component to stop
gas leak.
e. Turn thermostat below room temperature. Make sure main burner
and pilot flames go out.
OPERATION
Module operation can be conveniently divided into two phases for S8600H.
The phases are trial for ignition and main burner operation.
Page 15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents