Pacific hydrostar 95591 - .75 HP Set Up And Operating Instructions Manual page 9

Vertical float sump pump
Table of Contents

Advertisement

TO 115 VOLT, gROUndEd
gFCI OUTLET
BASE
(25)
3.
Connect the Discharge Pipe to the Base (25). nOTE: Make sure the Discharge
Pipe is secured to a solid surface, with appropriate hardware (not included), to
ensure the stability of the Pump. (See Figure E.)
4.
Install an additional union (not included) or other means of separating the Dis-
charge Pipe just above the floor to facilitate removal of the Pump if necessary.
(See Figure E.)
5.
A check valve (not included) is recommended just above, or in place of, the union
to prevent the backflow of water after each pump cycle. If a Check Valve is used,
a 1/8" diameter air bleed hole should be drilled through the Discharge Pipe just
above the lower Base (25) to prevent Pump "airlock". A small spray of water out of
this hole is normal while the Pump is running. (See Figure E.)
SKU 95591/95592/95593
FIgURE E
For technical questions, please call 1-800-444-3353
CHECK VALVE
OR
UnIOn
(nOT InCLUdEd)
o
dISCHARgE PIPE
(nOT InCLUdEd)
1/8"
AIR BLEEd HOLE
PAGE 9