Style
WARNING
To take power out from the TWIST
LOCK RECEPTACLE, insert the
plug into the receptacle, and turn
it clockwise to the lock position.
Be sure to ground the generator if
the connected electrical device Is
grounded.
NOTE :
When the
AC circuit breaker turns off during operation, the generator is over
loaded or the appliance is defective. Stop the generator immediately, check the
appliance and / or generator for overloading or detect and have repaired as
necessary by Makita factory or authorized service center.
CAUTION
The duplex 120V receptacle is protected by a GFCI (Ground Fault Circuit
Interrupter). GFCI shuts off the output current from the duplex 120V
receptacle when a ground fault occurs in the generator or the appliance.
Please note that other receptacles are not protected by GFCI.
Ampere
Receptacle
NEMA
up to 20A
5-20R
NEMA
up to 30A
L5-30R
NEMA
up to 30A
L14-30R
TABLE 1
15
AC plug
Description
GFCI (Ground Fault
NEMA
Circuit Interrupter)
Receptacle, duplex
5-20P
(REC1)
NEMA
Locking Receptacle
L5-30P
(REC3)
NEMA
Locking Receptacle
L14-30P
(REC4)
TWIST