SUZ-KA25VA.TH SUZ-KA25VAH.TH
SUZ-KA35VA.TH SUZ-KA35VAH.TH
MAX. REFRIGERANT PIPING LENGTH
Models
SUZ-KA25VA.TH
SUZ-KA35VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VAH.TH
MAX. HEIGHT DIFFERENCE
Indoor
unit
w Max. Height
difference 12m
w Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
Models
precharged
SUZ-KA25VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VA.TH
SUZ-KA35VAH.TH
Refrigerant piping
Max. length : m
A
20
(SLZ/SEZ)
Refrigerant Piping
Max. length
5m
6m
900
0
0
0
0
1,050
Piping size O.D : mm
Gas
Liquid
9.52
6.35
A
Refrigerant piping length (one way)
7m
8m
9m
10m
0
90
120
150
0
120
150
90
Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)
20
Outdoor unit
11m
12m
13m
14m
180
210
240
270
180
210
240
270
15m
20m
300
450
300
450