ICP PAMD75HB Installation Instructions Manual
ICP PAMD75HB Installation Instructions Manual

ICP PAMD75HB Installation Instructions Manual

Single package air conditioners paf & apfm series - 3 to 5 ton

Advertisement

Quick Links

Installation Instructions
SINGLE PACKAGE AIR CONDITIONERS
PAF & APFM Series - 3 to 5 TON
THREE PHASE
513 01 1102 O0
10-25-01
Printed in U.S.A.

Advertisement

Table of Contents
loading

Summary of Contents for ICP PAMD75HB

  • Page 1 Installation Instructions SINGLE PACKAGE AIR CONDITIONERS PAF & APFM Series - 3 to 5 TON THREE PHASE 513 01 1102 O0 10-25-01 Printed in U.S.A.
  • Page 2: Safety Labeling And Signal Words

    Danger Label Safety Labeling and Signal Words White lettering on a black background except the word DANGER which is white with a red background, Danger, Warning and Caution The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard.
  • Page 3 [IJ_lli I] hV4:1 l [.-'][I] l [.-_ 3 TO 5 TON All Dimensions In Inches "A" 1 3/4, 41/2. Detail 46-1/2 BASE PAN - CHASSIS 42-3/4"* © BASE RAIL BASE RAIL 46-1/4"* Condensate Drain SUPPLY 12-1/4 RETURN 1-9/16 2-3/16 2-3/16 3-3/4 UNIT SIZE 3 Ton...
  • Page 4: Safe Installation

    SAFE INSTALLATION Minimum Clearances to Combustible Construction Condenser Inlet ........30" Blower Service (Side) ......30" Control Service Side ....... 30" Clearance between 3 Ft. Overhang and Top of Unit ......30" Installation or repairs made by unqualified persons can result Combustible Base in hazards to you and others.
  • Page 5: Downflow Conversion

    Rooftop Installation outlet from trap MUST be at least 1" (25.4mm) below top of outlet from unit. Install the trap as near to the unit as Rooftop platform requirements: possible for proper drainage, - The unit MUST be situated to provide safe access for A3/4"...
  • Page 6: Line Voltage Wiring

    All exposed wiring and connections MUST be made with mounts inside the unit in the heater box. Field supplied line weatherproof cable or wire unless installed in conduit. voltage wires for the Electric Heat Accessory (separate from the field supplied line voltage wires to the unit) connect Thermostat to the circuit breaker(s) in the Electric Heat Accessory.
  • Page 7: Air Distributionsystem

    Air DistributionSystem For airflow data (blower performance data, blower speed NOTE: Connect supply and return air plenums to unit in a tap settings, etc.) see the Parts List. manner that will allow the top of the unit to be removed with- out removing plenums.
  • Page 8: Check Before Starting

    See next section, Speed Taps, to set the blower motor Check to see that clean, properly sized field supplied air filters are installed in the return air duct. speed terminal block (speed taps) determined in the following steps. Inspect the inside of the unit to be sure that all wires are in place and all tools, etc.
  • Page 9 Blower Motor Speed Taps - 208/230 Volt(3-Speed 4-Speed Motors) YELLO_L SPEED DATA IN UNITS TECHNICAL INFORMATION LABEL I BE SURE TO CHECK BLOWER MOTOR I ON THE UNIT Blower Motor Speed Taps- 460 Volt (3-Speed and 4-Speed Motors) SHOCK HAZARO OiSCONNEC1 POWER BEFORE SERVICING SPEED FROM...
  • Page 10: Operation

    Operation cycle and when the electric heat accessory is required if the Cooling electric heat accessory is installed. Adjust thermostat setting to desired temperature and set Adjusting Room Temperatures thermostat Heat-Cool switch to COOL. The unit will come on and operate automatically under control of the thermo- If the temperature in individual rooms is not as desired, bal- stat.
  • Page 11 To change speed tap settings, see Speed Taps in the Start- Annual Maintenance and Inspection up Procedures section of this manual. Condenser Fan Motor CAUTION FIGURE 8 Wire Colors Do NOT use 3 in 1 oil, penetrating oil, WD40 or similar oils to oil motor bearings, Oil the condenser fan motor after five years of operation and every five years thereafter.
  • Page 12: General Terms

    INTERNATIONAL COMFORT PRODUCTS LIMITED WARRANTY CERTIFICATE For Cooling & Heating Products SAVE THIS CERTIFICATE. It gives you specific legal rights, and you may also have other rights which may vary from state to state and province to province. If your unit needs servicing, contact a qualified dealer or qualified service technician of your choice. When requesting service, please have the model and serial number from each unit in your heating and/or cooling system readily available.
  • Page 13 ADDITIONAL TERMS FOR RESIDENTIAL APPLICATIONS ONLY The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page. Warranty coverage is limited to parts that fail due to defect in materials or workmanship during the specified term.