Trouble Shooting - Haier AU282XHERA Installation Manual

R410a multi split series room air conditioner outdoor unit
Hide thumbs Also See for AU282XHERA:
Table of Contents

Advertisement

Trouble shooting

FAILURE
STATE OF
CODE
LED 5-4-3-2-1
1
2
3
4
5
6
9
10
11
12
13
14
15
16
17
21
23
24
25
26
27
28
29
30
31
Take off the plastic cover on the right side of the unit, you can find the LEDs near the communication terminal.
Symbol means the LED is ON, and symbol means the LED is OFF.
TROUBLE
SHOOTING
Faulty defrost sensor Te
Faulty sensor Tao
Faulty sensor Ts
Faulty sensor Td
Input overcurrent
Abnormal communication
between indoor and outdoor
units
System high pressure
protection
System low pressure
protection
IPM protection
EEPROM fault
Over hot protection of
compressor
Over hot protection of SPDU
(or ISPM)
DC fan motor fault
Faulty 4-way valve
switching on
Faulty sensor Tc
Faulty sensor Toci
Low voltage protection
High voltage protection
Abnormal communication
between main PCB and
SPDU(or ISPM)
Compressor be locked
Compressor vibration too big Faulty compressor
Compressor lose position
Faulty compressor start
Faulty position checking
circuit
Compressor broken
POSSIBLE REASONS
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Over current of the system, or broken of the current
sensor,or malfunction with indoor or outdoor fan
motors, or faulty PCB.
Wrong connection, or the wires be disconnected, or
wrong address setting of indoor units, or faulty
PCB, or faulty power supply
High pressure switch is disconnected, or high
pressure switch worked, or Tc too high and faulty
outdoor fan motor when cooling, or faulty indoor
fan motors when heating, or refrigerant
overabundance
Low pressure switch is disconnected, or low
pressure switch worked, or Te too low and faulty
outdoor fan motors when heating, or faulty indoor
fan motor when cooling, or refrigerant shortage
IPM over current, or short circuit, or IPM
temperature too high, or IPM input voltage too
low,or faulty SPDU(or ISPM).
Faulty outdoor unit PCB
Serious lack of refrigerant of the system, or the
ambient temperature too high, or PMVs be
blocked
Ambient tempreatrue too high, or outdoor fan be
blocked, or bad air circulation of outdoor unit
Fan is blocked, or the terminal is disconnected
from the PCB
Coil of 4-way valve is disconnected, or faulty
outdoor PCB
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
VDC<194V, too low voltage from power source
VDC>400V, too high voltage from power source
Communication cables broken, or not be well
connected, or faulty main PCB, or faulty SPDU(or
ISPM)
Faulty compressor or SPDU(or ISPM)
Faulty SPDU(or ISPM)
Faulty compressor or SPDU(or ISPM)
Faulty SPDU(or ISPM)
Faulty compressor or SPDU(or ISPM)