Electric Wiring - Haier HDU-24H03/H Instruction Manual

Duct type
Table of Contents

Advertisement

INSTALLATION MANUAL FOR OUTDOOR UNIT
4
Open the valve rod for the 2-way valve to and angle of
anticlockwise 90 degree.
After 6 seconds later, close the 2-way valve and male
the inspection of gas leakage.
5
In case of gas leakage, tighten
parts of pipe connection. If
No gas leakage?
leakage stops, then proceed
steps.
6
Detach the charge hose from the service port, open
2-way valve and 3-way. Turn the valve rod
anticlockwise until hitting lightly.
7
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 2-way valve and 3-way's
a lottle more than the point where the torque increases
suddenly.
8
After attaching the each caps, check the gas leakage
around the caps.
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to make
all the refrigerant out, then charge the liquid refrigerant into air
conditioner according to the amount marked on the name plate.

5. Electric wiring

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal
lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)
Item
Phase
Model
HDU-42H03/H
HDU-24H03/H
HDU-28H03/H
6
DANGER OF BODILY INJURY OR DEATH
Circuit breaker
Switch breaker
Overcurrent protector
(A)
rated capacity (A)
3
30
1
40
2-way valve
3-way valve
Open
Service port
90
90
4 90 for 6 sec.
If it does not stop gas leakage, discharge whole refrigerants
from the serice port. After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas cylinder.
2-way valve
6
6
WARNING
Power source
wire size
(minimum)
20
2.5mm
26
4.0mm
25
2-way valve
3-way valve
Service port
Open
90
4
90 for 6 sec.
90
2-way valve
Liquid pipe 9.52mm
3-way valve
3-way valve
Gas pipe 19.05mm
6
6
2-way valve
3-way valve
Valve rod cap
7
Valve rod cap
7
7
Service port cap
2-way valve
3-way valve
Valve rod cap
7
7
Service port cap
Valve rod cap
7
Earth leakage breaker
Switch
Leak
breaker
current
30
30mA
2
2
40
30mA