Download Print this page

Generator Specifications; Engine Specifications; Voltage Regulator; Generator Features - Guardian 05650 Specifications

Guardian liquid cooled gas engine generator specifications

Advertisement

APPLICATION
& ENGINEERING DATA

GENERATOR SPECIFICATIONS

TYPE ................................................................................................................Synchronous
ROTOR INSULATION ................................................................................................ Class H
STATOR INSULATION .............................................................................................. Class H
TOTAL HARMONIC DISTORTION ..................................................................................<5%
TELEPHONE INTERFERENCE FACTOR (TIF) .................................................................. <50
ALTERNATOR OUTPUT LEADS 3 PHASE ....................................................................4 wire
BEARINGS...........................................................................................................Sealed Ball
COUPLING .............................................................................................................Flex Disk
LOAD CAPACITY (STANDBY RATING) ....................................................................... 80 kW
EXCITATION SYSTEM ...........................................................................................Brushless
NOTE:
Generator rating and performance in accordance with
ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.

VOLTAGE REGULATOR

TYPE ................................................................................................................... Full Digital
SENSING..................................................................................................................3 Phase
REGULATION ............................................................................................................± 1/4%
FEATURES............................................................................ Built into H-100 Control Panel

GENERATOR FEATURES

Revolving field heavy duty generator
Quiet drive coupling
Operating temperature rise 120 °C above a 40 °C ambient
Insulation is Class H rated at 150 °C rise
All prototype models have passed three phase short circuit testing

CONTROL PANEL FEATURES

TWO FOUR LINE LCD DISPLAYS READ:
• Voltage (all phases)
• Power factor
• kVAR
• Engine speed
• Run hours
• Fault history
• Coolant temperature
• Low oil pressure shutdown
• Overvoltage
• Low coolant level
• Not in auto position (flashing light)
• ATS selection
INTERNAL FUNCTIONS:
• I 2 T function for alternator protection from line to neutral and line to line short circuits
• Emergency stop
• Programmable auto crank function
• 2 wire start for any transfer switch
• Communicates with the Generac HTS transfer switch
• Built-in 7 day exerciser
• Adjustable engine speed at exercise
®
• RS232 port for GenLink
control
• RS485 port remote communication
• Canbus addressable
• Governor controller and voltage regulator are built into the master control board
C to 70 °C
• Temperature range -40 °
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
V/F Adjustable
Adjustable Voltage and Gain
• Current (all phases)
• kW
• Transfer switch status
• Low fuel pressure
• Service reminders
• Oil pressure
• Time and date
• High coolant temperature shutdown
• Overspeed
• Low coolant level
• Exercise speed

ENGINE SPECIFICATIONS

MAKE ...................................................................................................................... Generac
MODEL ......................................................................................................................V Type
CYLINDERS ....................................................................................................................... 8
DISPLACEMENT ..................................................................................................... 4.6 Liter
BORE............................................................................................................................. 3.55
STROKE ........................................................................................................................ 3.54
COMPRESSION RATIO ................................................................................................ 9.4:1
INTAKE AIR SYSTEM ..............................................................................Naturally Aspirated
VALVE SEATS ........................................................................................................ Hardened
LIFTER TYPE ......................................................................................................... Hydraulic
GOVERNOR SPECIFICATIONS
TYPE .....................................................................................................................Electronic
FREQUENCY REGULATION ...............................................................................Isochronous
STEADY STATE REGULATION ...................................................................................± .25%
All functions are factory preset.
Individual parameter adjustments can be made via GenLink
ENGINE LUBRICATION SYSTEM
OIL PUMP ..................................................................................................................... Gear
OIL FILTER ..................................................................................Full flow spin-on cartridge
CRANKCASE CAPACITY ......................................................................................... 5 Quarts
ENGINE COOLING SYSTEM
TYPE ......................................................................................................................... Closed
WATER PUMP ......................................................................................................Belt driven
FAN SPEED .................................................................................................................. 1600
FAN DIAMETER ..................................................................................................... 22 inches
FAN MODE .................................................................................................................. Puller
FUEL SYSTEM
FUEL TYPE ................................................................................Natural gas, vapor propane
CARBURETOR .....................................................................................................Down Draft
SECONDARY FUEL REGULATOR ........................................................................... Standard
FUEL SHUT OFF SOLENOID .................................................................................. Standard
OPERATING FUEL PRESSURE .......................................................................11" - 14" H 2 O

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR .....................................................................12V 30 Amp
STATIC BATTERY CHARGER ...............................................................................12V 2 Amp
RECOMMENDED BATTERY ..................................................................Group 24F, 525CCA
SYSTEM VOLTAGE.................................................................................................. 12 Volts
COMMERCIAL 80 kW
®
.

Advertisement

loading