Summary of Contents for SurgeX SU1000Li

  • Page 1 USER MANUAL SurgeX SU1000Li Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator / Power Conditioner...
  • Page 2: Table Of Contents

    SU1000Li Manual INTRODUCTION ............................2 INSTALLATION ............................2 ..........................2 VOLT CONNECTIONS ..........................2 ATTERY CONNECTION ........................2 CONNECTING YOUR EQUIPMENT ....................3 USB COMMUNICATIONS PORT CONNECTION ................3 PHONE MODEM NETWORK PROTECTION CONNECTION OPERATION .............................. 3 ..........................3 CHARGING THE BATTERY ...........................
  • Page 3: Introduction

    INSTALLATION The SurgeX SU 1000Li is designed to be installed in a 19 inch equipment rack and requires two units (2-U) of rack space. Remove the product from its packaging and slide it into place in the rack being careful to feed the power cord into the rack first and guide it so that it does not get caught or jammed as the product is installed.
  • Page 4: Usb Communications Port Connection

    SU1000Li Manual USB Communications Port Connection (optional) The Power Monitoring Software can be used with the UPS. Use the interface cable that comes with the UPS. Connect one end of the USB cable to the USB communications port on the rear panel of the UPS. Connect the other end of the USB cable to the device that will be monitoring/controlling the UPS.
  • Page 5: Led Indicators

    SU1000Li Manual LED INDICATORS There are four LED indicators located on the front panel. Their function is as follows: Surge SELF TEST (Green): When illuminated, the surge suppression circuitry is functioning correctly. Status LED and Alarm Table UPS Status Green LED...
  • Page 6: Troubleshooting

    SU1000Li Manual TROUBLESHOOTING Symptom Possible Cause What To Do UPS will not turn on On/Off button not pressed Press and release the On/Off button to start UPS UPS operates in battery mode only, Input AC circuit breaker is tripped Reset circuit breaker by pressing even though there is normal AC the plunger back in.
  • Page 7: Replacing The Battery

    SU1000Li Manual REPLACING THE BATTERY (Qualified Service Personnel Only) Please read all warnings and cautions before attempting to service the batteries. WARNING! This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by Qualified Service Personnel Only.
  • Page 8 SU1000Li Manual SPECIFICATIONS AC Input Number of Phases: Single (2W + G) Power Cord: 6-ft. grounded, 3 wire, #14 line cord Input Voltage (Acceptable Input Voltage): 120VAC (0 - 160VAC) Input Voltage Range (Normal mode): 90 - 150VAC DC Start Capability: Yes, (defaults to 60Hz)
  • Page 9: Specifications

    SU1000Li Manual Surge Protection Specifications Surge Protection: Advanced Series Mode® surge elimination Surge Energy Rating: 6,000 volts/3,000 amps Let through Voltage (6,000 volt surge): 0 volts UL 1449 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts;...