Page 3
Teledyne Isco recommends that you read this manual completely before placing the equipment in service. Although Teledyne Isco designs reliability into all equipment, there is always the possi- bility of a malfunction. This manual may help in diagnosing and repairing the malfunc- tion.
Page 6
3.3.4 Connecting the Level Sensor Cable to the QD Box ....3-7 3.3.5 Connecting the Cable from the QD Box to the 3020 ....3-7 3.4 Connection to a Sampler.
1.2 Description The 3020, shown in Figure 1-1, uses a submerged probe for level measurement. The flow transmitter will normally be used with some type of primary measuring device to measure flow in an open channel.
• Flow Transmitter-to-Sampler Connect Cable 1.4 The Submerged Probe The submerged probe, used by the 3020 Flow Transmitter as a level sensor, is shown in Figure 1-2, and is mounted in the flow stream. It measures liquid level by sensing changes in hydro- static pressure as level increases or decreases above it.
Figure 1-2 Submerged Probe Level Sensor (shown with standard tip) 1.5 Labels Adhesive labels are provided with the 3020 to allow the display and the mechanical totalizer to express values which are greater than the number of digits available in the unit. Where extremely large flow volumes are involved, trailing zeroes may be added to the display to make more meaningful numbers.
3020 Flow Transmitter Section 1 Introduction 1.6 Controls, Indicators, The controls, indicators, and terminal blocks of the 3020 Flow Transmitter are listed in Table 1-1, and their functions are and Terminal Blocks briefly described. Refer to Figure 1-3 for a view of the controls and indicators, and Figure 1-4 for a view of the connectors.
3020 Flow Transmitter Section 1 Introduction Fuse Figure 1-4 3020 Interior, Terminal Blocks Table 1-1 3020 Controls, Indicators, and Terminal Blocks Controls Function Keypad 22-Key, 6-column matrix. User programs flow transmitter through series of keystrokes prompted by messages on the display.
3020 Flow Transmitter Section 1 Introduction Table 1-1 3020 Controls, Indicators, and Terminal Blocks (Continued) 2312 Interface 3 #6 screws on Block TS2 Originally for connecting the 3020 to the Model 2312 strip chart plotter (obsolete). Terminals 8 (data), 9 (+), and 10(-) Currently used for connecting to other exter- nal serial devices or an alarm relay box.
3020 Flow Transmitter Section 1 Introduction Table 1-2 3020 Flow Transmitter Technical Specifications (Continued) External Totalizer Output 12 VDC pulse Operating Temperature - 20° F to 140° F (- 30°C to 65° C) Storage Temperature - 50° F to 150° F (- 60° C to 65° C)
Other equipment which may be used with the 3020 connects to the barrier blocks mounted on the power supply board in the bottom section of the flow transmitter's case.
2.2.1 Keypad Layout and The keypad is mounted in the middle of the left side of the 3020 Functions front panel. It is visible when the cabinet door is closed. The keypad has 23 keys arranged in six vertical columns.
The flow transmitter's program is stored in memory. 2.3 Programming The 3020 Flow Transmitter is programmed with the aid of the display. The keypad is used to enter program quantities and to control certain flow transmitter functions. The display is used to show selections chosen.
Page 20
2312. The 2312 is an electro-mechanical printer which records level or flow information from the 3020 on a strip chart to provide a hard copy of information measured by the flow transmitter. The 2312 printer is no longer sold by Teledyne Isco.
FLOW RATE AT MAXIMUM HEAD (0.001 to 9,999) Step 18 - Adjust Level Step 9 -Totalizer CURRENT LEVEL TOTALIZER To Remainder of Program (FT. –1.0 to 10.0)(M –0.31 to 3.05) SCALING (0 to 9,999) Figure 2-1 Simplified Flowchart Programming Flowchart for the 3020...
Section 2 Operation and Programming 2.3.2 List of Program Steps Following is a list of the program steps used in the 3020 along with the choices available or applicable range of values. Fol- lowing the list is a detailed explanation of the purpose for each step and the choices offered.
3020 Flow Transmitter Section 2 Operation and Programming Note Step 17 is programmed only if the 3020 is connected to exter- nal equipment which operates with the standard 4-20 mA cur- rent loop. 17. 4-20 mA Output Operation (level, flow rate, with or with- out event mark.)
Page 24
You would then enter 2 - 6 - 1 for this step. In this instance you would place three 0 labels and the CF label to the right of the display. If the 3020 is connected to a 2312, you would then enter 1 (CF) in Step 13 and 3 in Step 14.
Page 25
Steps 11 to 15 – Plotter Output - These steps need to be pro- grammed only if the 3020 is used with an Isco 2312 Plotter. Selections made in Steps 11 - 15 will determine the operation of the 2312. The selections made here do not affect the way the 3020 operates.
Page 26
This output, which is a variable DC current of 4-20 mA, changes with the level or flow rate measured by the 3020: 4 mA = 0% flow or 0 level; 20 mA = 100% flow rate, full-scale, or maximum head.
Commonly this is done by using a measuring staff. You may enter this level into the 3020 by adjusting the displayed level with the up and down arrow keys, or by entering the desired value with the numeric keys.
3020 Flow Transmitter Section 2 Operation and Programming Table 2-1 Equations Used in the 3020 Type and # of Device Flow Equation 1. V-Notch Weir Q = KH 2. Rectangular Weir Q = K(1.034H - 0.034H with End Contractions (see Section 2.4.3) 3.
Section 2 Operation and Programming 2.4 Programming In the following sections programming examples are described to show with keystroke entries how the 3020 Flow Transmitter is Examples set up for proper operation in specific applications. When pro- gramming the flow transmitter, note that the number on the left side of the display is the PROGRAM STEP while the number on the right is the current value.
Page 30
3020 Flow Transmitter Section 2 Operation and Programming 5. Enter the flow at maximum head, 1754 GPM. Press 1, 7, 5 1754 Press ENTER. Place the “GPM” label to the right of the display. 6. To enter the totalizer scaling, calculated above, press 1, 0, 5, 2.
9,999. The value entered into the 3020 will then be only four digits long (42,740 10 = 4,274). Place one 0 label and the GPM label to the right of the display.
Page 32
3020 Flow Transmitter Section 2 Operation and Programming 2. Select units of measure for level. To select feet, press 1. Press ENTER. 3. Select the correct primary device from the list shown on the front panel. To select a Cipolletti weir, press 4.
Page 33
3020 Flow Transmitter Section 2 Operation and Programming 7. Press SAMPLER OUTPUT to program sampler pacing. To enter the number calculated above, press 2, 5, 6, 4. 10 2564 Press ENTER. XXXX (Flow Rate) 8. Press PLOTTER to set up the output for the plotter. The first requirement is to select the units of flow rate dis- played on the plotter.
Page 34
3020 Flow Transmitter Section 2 Operation and Programming 12. To reset the totalizer on the remote plotter (Isco Model 2312) to 0, press 1. Press ENTER. XXXX (Flow Rate) 13. Press DISPLAY. To alternate between level and flow rate, press 3.
2% of full flow accuracy for crest-to-maximum-head ratios of 2 to 10. If more accuracy is required, then you must select #34, the equation. (See Section 2.4.3) The equation programmed into the 3020 is in the general form: ...
= maximum head in feet. N1 + N2 = flow rate at maximum head. 2.4.4 Programming Example The following example involves programming the 3020 with an Using an Equation equation. The installation has a device whose level-to-flow rate conversion follows the equation: ...
Page 37
1000 gallons, divide 160,056 GPH by 1,000 (160,056 GPH 1,000 gallons per count = 160 counts per hour). The result, 160, is the value entered into the 3020. Place three 0 labels and the GAL label to the right of the totalizer.
Page 38
3020 Flow Transmitter Section 2 Operation and Programming 8. To enter the maximum expected head for the above equa- tion, press 2, (decimal), 5. Press ENTER. 9. To program the totalizer, enter the constant calculated above by pressing 1, 6, 0.
P1, P2 = exponents To change the level-to-flow rate conversion for a rectangular weir with end contractions into an equation that can program into the 3020, calculate the constants N1 and N2: N1 = 3.33(L)(H N2 = 3.33(-0.2)(H Where:...
3020 Flow Transmitter Section 2 Operation and Programming If a flow rate other than CFS is desired, it is necessary to convert these values from CFS to the desired units of measure. For example, consider a 4 foot rectangular weir with end con- tractions and a maximum head of 2 feet.
Page 42
3020 Flow Transmitter Section 2 Operation and Programming Place one 0 label and the GPM label to the right of the display. To totalize in cubic feet, we must first calculate the total flow per hour of flow rate at maximum head. 52.74 CFS x 60 seconds per minute x 60 minutes per hour = 189,864 cubic feet per hour (CFH).
Page 43
3020 Flow Transmitter Section 2 Operation and Programming Place one “0” label and the “GPM” label to the right of the display. Press ENTER. 8. To enter the maximum head, press 2. Press ENTER. 9. To program the totalizer in thousands of cubic feet, enter 190.
3020 and an automatic wastewater sampler. 3.1 General Comments on While the 3020 may be used for portable or temporary flow moni- toring, it is generally intended for permanent installation, as Installation connection to a commercial power source is necessary. You may...
1000 feet (305 m). 3.1.3 Portable Operation The 3020 can be used for temporary monitoring of a flow stream, limited by the 75 ft. distance to the transducer and, more impor- tantly, by the availability of 120 VAC power for the flow trans- mitter.
Source current power input. Teledyne Isco recommends connecting the 3020 to its own separate branch circuit in the main circuit breaker panel or local branch panel. Label the breaker with its use. A 15 Ampere breaker is sufficient. A separate cutoff switch next to the main panel, clearly labeled, is also acceptable.
HAZARD OF ELECTROCUTION! You can be KILLED if you accidentally contact the 120 VAC power supplied to the 3020. Do not attempt to wire the 3020 live or perform any work on the unit with power connected and the protective covers removed.
5-pin male M/S connector. Plug this connector into the mating M/S connector coming out of the 3020 cabinet. Make sure the connectors are threaded tightly together. The allowable distance between the flow transmitter and the submerged probe is increased to 75 feet (22.8 m) if the optional extension cables are used.
Box. The Quick-Disconnect Box contains a terminal strip. Cable attached to these terminals may run as far as 1000 feet (305 m) to connect to the flow transmitter. Teledyne Isco has suitable cable available for this purpose, or you can supply your own cable.
3020 Flow Transmitter Section 3 Installation 3.3.3 Preparing Shielded If you use shielded cable to connect the flow transmitter to the Cable Quick-Disconnect Box, use care preparing the ends. Avoid cutting too deeply and nicking the insulation on the wires or damaging the braided shield.
You can connect an Isco sampler and the flow transmitter together two different ways. 3.4.1 Sampler Located If the Isco Sampler is located within 22 feet of the 3020 Flow Within 22 Feet Transmitter, a 22 foot (7.6 m) connect cable is available from Teledyne Isco that has wire terminations on one end and a 6-pin M/S Connector on the other.
3.5 Connection to Other There are other optional accessories which may be used with the Equipment 3020 Flow Transmitter. These devices are discussed in detail in Section 4. Among these devices are: • Remote Totalizer • 2410 Circular Chart Recorder •...
3020 Flow Transmitter Section 3 Installation If you want to measure flow using a gravity flow equation, such as the Manning equation, you will generally install the probe in the entrance (upstream) pipe of a manhole. If you want to measure flow by calibrating a manhole invert, you would probably locate the probe directly in the manhole invert.
3.9 Submerged Probe Teledyne Isco provides three nose sections, each designed for spe- Nose Sections cific flow stream conditions. A complete list of nose sections and their part numbers can be found in Appendix A.
These mounting rings are available for use in pipes with inside diameters of 6" (15.2 cm), 8" (20.3 cm), 10" (25.4 cm), 12" (30.5 cm), and 15" (38.1 cm). The Teledyne Isco part numbers for the various size mounting rings available are listed in Appendix B.
3020 Flow Transmitter Section 3 Installation Compress ring into gap to install in pipe, then..outward force of ring against pipe wall holds ring in place inside pipe. Figure 3-6 Sensor Installed on a Spring Ring Attaching the Sensor to the Attach the probe to the ring either by using two 4-40 x "...
3020 Flow Transmitter Section 3 Installation Figure 3-7 Spring Ring Preparation Figure 3-8 Mounting Ring in a Round Pipe CAUTION Make sure the sensor cable is securely fastened along the back (downstream) edge of the ring. Otherwise, the sensor may provide inaccurate level readings under conditions of high velocity.
3.10.2 Scissors Rings For pipes larger than 15" in diameter, Teledyne Isco offers the adjustable Scissors Ring (also known as the Universal Mounting Ring). This device consists of two or more metal strips that lock together with tabs to form a single assembly.
Many installations require mounting methods other than Techniques mounting rings. Some alternative mounting methods are described below. Contact Teledyne Isco for assistance in deter- mining your specific installation needs. 3.11.1 Rectangular and A flat, anchored mounting plate is a common mounting choice for Trapezoidal Channels installing sensors in rectangular or trapezoidal channels.
3020 Flow Transmitter Section 3 Installation 3.11.2 Stilling Wells or In flow streams with a minimal flow velocity or in a stilling well, Streams with Very Low simply attach the probe to a weighted plate and submerge the Velocity plate in the stream or stilling well.
1. Handle Flume 2. Ring Base Bottom Assembly Parshall Flume Round Pipe Probe Mounted Contact the factory or your Teledyne Isco in Recess Representative for additional information about the Street Level Installation system. Figure 3-11 Typical Primary Device Installations 3-18...
3020 Flow Transmitter Section 3 Installation Mounting hardware may have to be fabricated locally to allow the level sensor to be mounted at the correct location in the primary device. The only requirements for custom mounting hardware are: • The probe must be securely attached to the side or bottom of the flow stream.
4.1 High-Low Alarm Relay Teledyne Isco offers an alarm box that monitors flow rate infor- mation provided by the 3020 (see Figure 4-1). Relays trip when flow rate falls below or exceeds preset limits. High and low set points are user-selected and range from 0% to 99% in 1% incre- ments.
The High-Low Alarm Relay Box contains a microprocessor that Switches compares serial data from the 3020 to set values for high and low alarm trip-points for the relays. Rotary switches inside the alarm box set the trip points. There are two rotary switches for each limit.
Any color of wire or cable is acceptable, but make sure the connections end up the same as those shown. The maximum recommended distance between the 3020 and the alarm box is 250 feet (76 meters). The recommended wire gauge for interconnection cable is #18 AWG.
Devices a simplex serial output port providing ASCII level and flow rate data for remote transmission. Every 30 seconds, the 3020 transmits a line of data which includes level, units of level mea- surement, percentage of maximum flow rate, maximum flow rate, a total-flow value, units of flow, sample number, and bottle number.
‘CR’ (carriage return) and an ‘LF’ (line feed). The large gaps between some of the words indicate extra character spaces which are defined for a 2312 plotter, but not for the 3020. 4.3 Remote Totalizer Teledyne Isco offers a remote totalizer for use with the 3020. It...
3020 Flow Transmitter Section 4 Options and Accessories 4.4 Extension Cables for The submerged probe level sensor used with 3020 has a 25 foot (7.6 m) or 50 foot (15.2 m) cable attached, depending upon the the Sensor transducer measuring range. This cable terminates in a 5-pin male M/S connector which plugs into a mating M/S connector at the 3020.
Teledyne Isco recommends becoming completely familiar with the routine maintenance procedures presented here. While the 3020 is ruggedly built to withstand severe field conditions, it will function best and remain most reliable if these simple procedures are learned and followed.
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting 5.2 Regenerating the The 3020 includes a desiccant cartridge as part of the instal- lation. This is a plastic tube filled with particles and attached to Desiccant Cartridge the flow transmitter (or Quick-Disconnect Box) with a clamp and a silicone rubber tube.
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting CAUTION Do not attempt to regenerate the desiccator by placing the entire cartridge in an oven. The cartridge is plastic and will melt. Do not use a microwave oven. Do not allow moisture to enter the reference tube for the submerged probe.
If level readings become erratic or erroneous, return the probe to Teledyne Isco Technical Service for evaluation. 5.3.2 Cleaning the Occasionally, organic materials may become jammed inside the Submerged Probe submerged probe's housing.
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting Figure 5-1 Warning Disk Inside Probe Again, any deformation of the stainless steel diaphragm will per- manently disable the submerged probe. If you must remove the nose of the probe, do it very carefully. A small warning disk is located in front of the transducer.
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting In permanent installations, cables repeatedly subjected to rough environments will fail and should be installed in conduit for pro- tection. The conduit must be large enough to pass the M/S con- nectors, as you cannot remove or replace them.
Page 77
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting CAUTION The 3020 circuit boards contain CMOS semiconductors, which are easily destroyed by the discharge of static electricity. Do not attempt troubleshooting or repair at the job site. Return the board to the factory for servicing or make repairs at an appro- priately-equipped service area.
5.5 Display Warnings The 3020 LCD displays various error messages to warn the user of problems in the program, or difficulties inside the flow trans- mitter. Messages will generally assume the format of:...
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting CAUTION Do not attempt to service the 3020 Flow Transmitter unless skilled in the analysis and repair of digital circuits. You must also know how to work safely on AC-powered equipment, as a real safety hazard is present here.
• Make sure the crystal oscillator is running and at the proper frequency. 5.7.2 Precautions for The 3020 is a low-voltage, DC-powered device, and hazardous Servicing AC-Powered voltages are not present on the CPU board. However, the unit Equipment converts power from 120 or 240 VAC to the DC used to run the flow transmitter.
5.7.3 Precautions for Most of the circuitry in the 3020 is made up of CMOS compo- Servicing CMOS nents. Because of the oxide gate structure of these devices, they...
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting environments. Conductive grounding mats are available for workstations and are the best solution for discharging static and allowing safe repair of AC-powered equipment. • The degree of hazard depends on the level of humidity.
U11 is the microprocessor that controls the rest of the board and performs level and flow calculations. The submerged probe transmits pressure to the 3020 as a voltage that is proportional to pressure, which is also proportional to depth. U3 converts this voltage to a digital number, which is sent to the microprocessor.
3020 Flow Transmitter Section 5 Maintenance and Troubleshooting U14 and U10 are optocouplers used to optically isolate the 4 to 20 mA current loop from the rest of the electronics. U9 converts the serial data coming from U14 into parallel data for U8 which is a D to A converter.
3020 Flow Transmitter Appendix A Replacement Parts and Accessories A.1 Replacement Parts Replacement parts are called out in the following pages, followed by a list of accessories. Refer to the callout in the adjacent table List to determine the part number for the item.
Page 88
3020 Flow Transmitter Appendix A Replacement Parts and Accessories...
Page 89
3020 Flow Transmitter Appendix A Replacement Parts and Accessories...
Page 90
3020 Flow Transmitter Appendix A Replacement Parts and Accessories...
Appendix B Programming Worksheets The following is a worksheet for the user to select desired entries for each step of the 3020 program. Make several photo copies of this sheet. It is suggested that the user circle selected entries with a pencil; where numeric values are required, they may be written in.
Page 94
(range: 0.001 to 9,999) Step 9: Enter Totalizer Scaling _____________ (range: 0 to 9,999) Program the following step only if the 3020 is connected to an automatic wastewater sampler. Press the SAMPLER OUTPUT key. Step 10: Enter Sampler Scaling ______________...
Page 95
3020 Flow Transmitter Appendix B Programming Worksheets Program Steps 10 to 14 only if the 3020 is connected to a 2312 Plotter. Press the PLOTTER OUTPUT key. Step 11: Enter Units of Measure for Flow Rate on the Remote Plotter ______________ 1.
Page 96
3020 Flow Transmitter Appendix B Programming Worksheets...
The second section deals with the special problem of hazardous gases found in sewers. WARNING The 3020 Flow Meter has not been approved for use in hazardous locations as defined by the National Electrical Code.
Page 98
3020 Flow Transmitter Appendix C General Safety Procedures “Sharp Edges. Sharp edges of items in or near a manhole may cause cuts or bruises. “Lifting Injuries. Unless proper tools are used to remove manhole covers, back injuries or injuries to hands or feet may result.
Page 99
3020 Flow Transmitter Appendix C General Safety Procedures also function as guards to keep people and vehicles away from the manhole opening. To avoid a serious injury, a person should not be lifted out of a manhole by his arm unless it is a dire emer- gency.
3020 Flow Transmitter Appendix C General Safety Procedures “10. Field Equipment. The following equipment will be available for use: Blowers Gloves Traffic cones Breathing apparatus Hard Hats Coveralls Harnesses First aid kits Manhole irons Emergency flashers Pick axes Flashlights Rain slickers...
Page 101
3020 Flow Transmitter Appendix C General Safety Procedures “It seems unlikely that anyone has ever died in a sewer from suf- focation, that is, a lack of oxygen. Deaths have often been attributed to ‘asphyxiation.’ This is a word which, according to the dictionary, is used to mean death from an atmosphere that does not support life.
3020 Flow Transmitter Appendix C General Safety Procedures number of harmful vapors. They, too, are sensed by smell and explosimeter tests if they get into the public sewer. Such occur- rences are rare. “The attempt to instill a sense of urgency about real hazards is diluted if a man is told to give attention to a long list of things that in fact are irrelevant.
Page 103
3020 Flow Transmitter Appendix C General Safety Procedures Table C-1 Hazardous Gases (Continued) Specific Explosive Likely Max. Safe Simplest and Gravity Range (% by Location Most Chemical Common Physiological Safe 60 8 Hour Cheapest or Vapor vol. in air) Common...
Page 104
3020 Flow Transmitter Appendix C General Safety Procedures Table C-1 Hazardous Gases (Continued) Specific Explosive Likely Max. Safe Simplest and Gravity Range (% by Location Most Chemical Common Physiological Safe 60 8 Hour Cheapest or Vapor vol. in air) Common...
Page 105
3020 Flow Transmitter Appendix C General Safety Procedures Table C-1 Hazardous Gases (Continued) Specific Explosive Likely Max. Safe Simplest and Gravity Range (% by Location Most Chemical Common Physiological Safe 60 8 Hour Cheapest or Vapor vol. in air) Common...
Page 106
3020 Flow Transmitter Appendix C General Safety Procedures C-10...
This appendix provides Material Safety Data Sheets for the des- iccant used by the 3020 Flow transmitter. Teledyne Isco cannot guarantee the accuracy of the data. Specific questions regarding the use and handling of the products should be directed to the manufacturer listed on the MSDS.
Page 108
3020 Flow Transmitter Appendix D Material Safety Data Sheets Indicating Silica Gel Material Safety Data Sheet Identity (Trade Name as Used on Label) Manufacturer MSDS Number* : MULTISORB TECHNOLOGIES, INC. (formerly Multiform Desiccants, Inc.) Address: CAS Number* : 325 Harlem Road...
Page 109
3020 Flow Transmitter Appendix D Material Safety Data Sheets Page 2 Section 5 - Health Hazard Data PRIMARY ROUTES Inhalation Ingestion CARCINOGEN OSHA OF ENTRY Skin Absorption Not Hazardous LISTED IN IARC Monograph Not Listed Acute HEALTH HAZARDS May cause eye, skin and mucous membrane irritation.
Page 110
3020 Flow Transmitter Appendix D Material Safety Data Sheets MATERIAL SAFETY DATA SHEET Effective Date March 8, 2005 M163 MSDS Number Section 1 Product and Company Information Product Name: Silica gel, indicating, yellow Desiccant, absorbent Product Use: Grades: Silica gel, indicating...
Page 111
3020 Flow Transmitter Appendix D Material Safety Data Sheets Section 4 First Aid Measures Eyes: Rinse the eyes well with water while lifting the eye lids. If irritation persists, consult a physician. Wash affected area with soap and water.
Page 112
3020 Flow Transmitter Appendix D Material Safety Data Sheets Section 8 Exposure Controls/Personal Protection Use exhaust ventilation to keep the airborne concentrations below the exposure Engineering Controls: limits. Respiratory Protection: Use NIOSH approved respirator when the air quality levels exceed the TLV's.
Page 113
3020 Flow Transmitter Appendix D Material Safety Data Sheets Section 11 Toxicological Information This product and its components are not listed on the NTP or OSHA Carcinogen lists. Animal Toxicology Tests for DOT Hazard classification ( Tests Conducted on finely ground silica gel) 1 - hour LC (rat) >...
Page 114
3020 Flow Transmitter Appendix D Material Safety Data Sheets Section 16 Other Information HMIS Hazardous Materials Identification System HMIS Rating Health Flammability Reactivity 0 - minimal hazard, 1 - slight hazard, 2 - moderate hazard, 3 - serious hazard, 4 - severe hazard This MSDS was prepared by: George E.
Page 115
3020 Flow Transmitter Index Numerics 2410 Circular Chart Recorder, 4-6 Level Adjustment, 2-10 4-20 mA Output, 2-10 Maintenance Accessories and Spare Parts, A-5 Desiccant, 5-2 Alarm Box, 4-1 Submerged Probe, 5-3 Analog Output, 2-10 Transmitter Case, 5-1 Material Safety Data Sheets, D-1...
Page 117
Lincoln, NE 68504, U.S.A. customer’s facility and the repair facility. * This warranty applies to the USA and countries where Teledyne Isco Inc. does not have an authorized dealer. Customers in countries outside the USA, where Teledyne Isco has an authorized dealer, should contact their Teledyne Isco dealer for warranty service.