Environmental Specifications; Table 27. Environmental Specifications - Dell PowerEdge R820 Technical Manual

Four-socket, 2u rack server
Hide thumbs Also See for PowerEdge R820:
Table of Contents

Advertisement

Environmental specifications

Table 27 details the environmental specifications for the R820. For additional information about
environmental measurements for specific system configurations, see
Dell.com/environmental_datasheets.
Fresh Air: temperature, humidity, altitude de-rating
Continuous
10°C to 35°C (50°F to 95°F) at 10% to 80% relative humidity with 26°C (78.8°F) maximum
operation
dew point (maximum wet bulb temperature). De-rate maximum allowable dry bulb
temperature at 1°C per 300m above 950m (1°F per 547 ft above 3117 ft).
Expanded
When operating in the expanded temperature range, system performance may be impacted,
operation
and ambient temperature warnings may be reported on the LCD and in the System Event
Log.
≤ 10% of annual operating hours: 5°C to 10°C and 35°C to 40°C (with no direct sunlight on
the equipment) at 5% to 85% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours. For
temperatures between 35°C and 40°C (95°F to 104°F), de-rate maximum allowable dry bulb
temperature by 1°C per 175m above 950m (1°F per 319 ft above 3117 ft).
≤ 1% of annual operating hours: –5°C to 5°C and 40°C to 45°C (with no direct sunlight on
the equipment) at 5% to 90% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours. For
temperatures between 40°C and 45°C (104°F to 113°F), de-rate maximum allowable dry bulb
temperature by 1°C per 125m above 950m (1°F per 228 ft above 3117 ft).
Expanded operation restrictions:
GPU
-
LRDIMM
-
Temperature
Operating
See Fresh Air for temperature information
o
Storage
–40
C to 65
48
PowerEdge R820 Technical Guide
Table 27.
Environmental specifications
No cold startup below 5°C
Maximum 95W processors (two or four processors)
Maximum 8 hard drives (no dual PERC)
Maximum altitude for the operating temperature must be 3050m (10,000ft)
x8 backplane only (restrict 2nd x8, x16 or x4 backplanes)
Requires two redundant power supplies, either 750W or 1100W
PCIe slot 1 and slot 2 cannot be populated
Not supported:
o
o
o
C (-40
F to 149
F) with a maximum temperature gradation of 20
o
C per hour

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents