WATER HEATER LOCATION
◊
Centrally located with the water piping system. Located as close
to the gas piping and vent pipe system as possible.
◊
Located indoors and in a vertical position. Protected from freezing
temperatures.
◊
Proper clearances from combustible surfaces maintained and not
installed directly on a carpeted floor. Sufficient room to service
the water heater.
◊
Provisions made to protect the area from water damage. Properly
sized drain pan installed and piped to an adequate drain.
◊
Installation area free of corrosive elements and flammable
materials.
GAS SUPPLY AND PIPING
◊
Only rigid piping used. No flexible or copper gas connections.
◊
Gas supply is the same type as listed on the water heater data
plate.
◊
Gas line equipped with full opening shut-off valve, union and drip
leg.
◊
Approved pipe joint compound used.
◊
Adequate pipe size and of approved material.
◊
Chloride-free soap and water solution or other approved means
used to check all connections and fittings for possible gas leaks.
CONDENSATE LINE
◊
Proper piping material.
◊
Line sloped to adequate drain or approved condensate pump.
◊
Protected from freezing (if required).
◊
Properly vented.
WATER SYSTEM PIPING
◊
Temperature and pressure relief valve properly installed with a
discharge line run to an open drain and protected from freezing.
◊
All piping properly installed and free of leaks.
◊
Heater completely filled with water.
◊
Closed system pressure build-up precautions addressed.
◊
If required, tempering valve or anti-scald device installed per
manufacturer's instructions
20
INSTALLATION CHECK LIST
ELECTRICAL
VENT PIPE SYSTEM
VENT TERMINATION
◊
Unit connected to a dedicated 120 volt, 15 ampere supply.
◊
Proper polarity.
◊
Water heater properly grounded.
◊
Installed per the latest edition of the National Electric Code,
ANSI/NFPA 70 or prevailing local codes.
◊
Vent pipe and fittings of approved material.
◊
Acceptable length and number of elbows on air inlet pipe.
◊
Acceptable length and number of elbows on exhaust pipe.
◊
Installed in accordance with "National Fuel Gas Code", NFPA
54, ANSI Z223.1-Latest Edition or prevailing provisions of local
codes.
◊
All horizontal piping sloped upward 1/4" per foot.
◊
Not obstructed in any way.
CONCENTRIC
◊
12" min. above grade/snow level
◊
Exhaust pipe/air intake pipe sloped downwards toward water
heater.
HORIZONTAL
◊
Correct relationship - exhaust to intake
◊
12" min. above grade/snow level
◊
Exhaust pipe/air intake pipe sloped downwards toward water
heater.
ALTERNATE HORIZONTAL
◊
Correct relationship - exhaust to intake
◊
12" min. above anticipated snow level
◊
Exhaust pipe/air intake pipe sloped downwards toward water
heater.
VERTICAL
◊
Intake - 12" min. above roof/snow level
◊
Correct relationship - exhaust to intake.