Gas Supply And Piping - Polaris GAS WATER HEATER Installation, Operation And Service Manual

High efficiency gas water heater
Table of Contents

Advertisement

GENERAL INFORMATION
DANGER
THIS WATER HEATER IS EQUIPPED FOR
ONE TYPE OF GAS ONLY. DO NOT USE THIS
WATER HEATER WITH ANY GAS OTHER
THAN THE ONE LISTED ON THE DATA
PLATE LOCATED ON THE WATER HEATER
JACKET. FAILURE TO USE THE CORRECT
GAS CAN RESULT IN PROPERTY DAMAGE,
BODILY INJURY, OR DEATH.
TABLE 2
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in.
and specific gravity of 0.60 (natural gas).
Nominal
Iron Pipe
Size, Inches
10
20
1/2
132
92
3/4
278
190
1
520
350
1-1/4
1050
730
1-1/2
1600
1100
After the length of pipe has been determined, select the pipe size which will provide the minimum cubit feet per hour required for the gas input rating of the water
heater. By formula:
Cu. Ft. Per Hr. Required =
The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT3) may be determined by consulting the local
natural gas utility.
TABLE 3
LP GAS PIPE CAPACITY TABLE
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure). Based on a Pressure
Drop of 0.5 Inch Water Column.
Nominal iron
pipe size, in.
10
20
1/2
275
189
3/4
567
393
1
1071
732
1-1/4
2205
1496
Example: Input BTU requirement of the water heater, 100,000 BTUH
Total pipe length, 80 feet = 3/4" IPS required.

GAS SUPPLY AND PIPING

GAS PIPING
This water heater must only be connected
to gas supplied by a commercial supplier.
Install the gas piping according to all local and
state codes or with the "National Fuel Gas
Code", ANSI Z223.1 (NFPA 54) - Latest
Edition.
Do not use copper or brass piping and fittings.
Do not use flexible connectors. Use only rigid
pipe.
Table 2 and or Table 3 are provided as a
sizing reference for commonly used gas pipe
materials. Consult the "National Fuel and Gas
Code" for the recommended gas pipe size of
other materials.
Length of Pipe, Feet
30
40
50
60
73
63
56
50
152
130
115
105
285
245
215
195
590
500
440
400
890
760
670
610
Gas Input of Water Heater (BTU/HR)
Heating Value of Gas (BTU/FT³)
Len
gth of Pipe, Feet
30
40
50
152
129
114
315
267
237
590
504
448
1212
1039
913
70
80
90
100
46
43
40
38
96
90
84
79
180
170
160
150
370
350
320
305
560
530
490
460
60
70
80
90
103
96
89
217
196
185
409
378
346
834
771
724
DANGER
THE GAS LINE MUST BE OF ADEQUATE
SIZE SO AS TO PREVENT UNDUE
PRESSURE DROP AND NEVER SMALLER
THAN THE PIPE SIZE TO THE GAS VALVE
ON THE WATER HEATER. FAILURE TO
PROPERLY SIZE THE GAS LINE CAN
CAUSE A FIRE OR EXPLOSION RE-
SULTING IN PROPERTY DAMAGE, BODILY
INJURY OR DEATH.
125
150
75
200
34
31
28
72
64
59
130
120
110
275
250
225
410
380
350
100
125
150
83
78
69
63
173
162
146
132
322
307
275
252
677
630
567
511
26
55
100
210
320
17