Figure 12. Charging Chart For 4 Ton Units; Figure 13. Charging Chart For 5 Ton Units - Nordyne NS6QD SERIES User's Manual & Installation Instructions

Outdoor split system air conditioner with quick connect couplings
Table of Contents

Advertisement

600
575
550
525
Remove refrigerant when above curve
500
475
450
425
400
375
350
325
300
275
250
75
80
NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
75
18
NS6QD-048K TXV Charging Chart
85
90
95

Figure 12. Charging Chart for 4 Ton Units

NS6QD-060K TXV Charging Chart
Remove refrigerant when above curve
80
85
90
95

Figure 13. Charging Chart for 5 Ton Units

100
105
110
Liquid Temperature ( ° F)
Add refrigerant when below curve
100
105
110
Liquid Temperature ( ° F)
Add refrigerant when below curve
115
120
125
115
120
125
130
130
135
135