Cold Weather Kit; Reconfiguring The Fuel System - Generac Power Systems Guardian Elite 005259-0 Owner's Manual

2.4l 35kw standby generator
Table of Contents

Advertisement

CONTROL PANEL
GENERATOR
CONNECTION
BOX
120 Volt +
Neutral
Grd
Ground Level
Concrete Slab

COLD WEATHER KIT

For cold climates, optional cold weather kit (part
number 0F6148) is recommended. The kit includes:
• Battery Warmer
• 4" Junction Box with hardware
• 6 qt. pack 5W-30 synthetic oil (engine)

RECONFIGURING THE FUEL SYSTEM

All models are configured for natural gas or LP
vapor from the factory.
To reconfigure the fuel system from NG to LP , follow
these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet
port (Port 1) of the demand regulator (Figure
6.2).
3. Remove the brass hose fitting from the outlet port
(Port 1) of the demand regulator.
4. Remove the brass hose fitting with solenoid from
Port 2.
5. Install brass hose fitting into Port 2.
6. Install the brass hose fitting with solenoid into
Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure
and type for configuration.
02/06
0
Rev.
GenSpec019
Standby Generator Sets
Figure 1 — Interconnections
TO
ALTERNATOR
N1
NEUTRAL
N2
23
194
CIRCUIT
BREAKER
183
178
Battery
Charger
Input
GROUND
FRAME RAIL
STUB-UP AREA
See Install Dwg for
Dimensions
NOTE:
Specifications
Transfer Switch
4- # 14 GA
WIRES TO
GENERATOR
CONNECTION
BOX
10. Reverse the procedure to convert back to natural
gas.
11. The Dip switch inside the control panel must be
in the LP or NG position when switching to differ-
ent fuels.
Figure 6.2 — Reconfigure the Fuel System
Port 1 is for NG only and Port 2 is for LP vapor
only. No provision for dual fuel has been made.
Serious injury or damage may occur if not con-
figured properly. Please consult an Authorized
Service Dealer with any questions.
6-2
Utility In
NEUTRAL
Gen
N1
N2
23
194
Load
186
Out
178
TO GENERATOR
CONNECTION BOX
To Generator Control Panel
CIRCUIT BREAKER SIZE
KW
VOLTS
/
AMPS
LUG SIZE
35
240 1 Ø
175
#6 to 300 mcm
35
208 3 Ø
150
#6 to 300 mcm
35
480 3 Ø
60
#6 to 300 mcm
NOTE:
DANGER

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents