Standby Power Rating
130 kW
STANDARD EQUIPMENT
• All input connections in one single area
• High coolant temperature shutdown
• Low oil pressure shutdown
• Low coolant level automatic shutdown
• Low fuel pressure
• Overspeed automatic shutdown
• Adjustable cranking timer
• Adjustable exercise timer
• Oil drain extension
• Cool flow radiator
• Closed coolant recovery system
FEATURES
• Innovative design and fully prototype tested
• UL 2200 Listed
• Solid state frequency compensated voltage regulator
• Dynamic and static battery charger
• Sound attenuated acoustically designed enclosure
• Whisper-Test™ for low noise level exercise
• Acoustically designed engine cooling system
• High flow low noise factory engineered exhaust system
• State of the art digital control system with H-100
microprocessor control panel
60 Hz
Liquid Cooled Gas Engine Generator Sets
• UV/Ozone resistant hoses
• Watertight state of the art electrical connectors
• Mainline circuit breaker
• Oil drain extension to frame rail
• Radiator drain extension
• Battery charge alternator
• 2 Amp static battery charger
• Battery, battery rack and battery cables
• Fan and belt guards
• Isochronous governor
• Flex fuel line pigtail
• Built-in kW, kVAR and power factor meters
• Watertight electrical connectors
• Rodent proof construction
• High efficiency, low distortion Generac designed alternator
• Vibration isolated from mounting base
• Matching Generac transfer switches engineered and
tested to work as a system
• All components easily accessible for maintenance
• Electrostatically applied powder paint
COMMERCIAL SERIES
Whisper-Test™

Low Speed Exercise

65 dB(A) at 23 feet
GENERAC 6.8L ENGINE
Naturally Aspirated
Gaseous Fueled
UL 2200 Listed
Transfer Switch is sold separately

Advertisement

loading

Summary of Contents for Generac Power Systems Liquid Cooled Gas Engine Generator Sets None

  • Page 1: Low Speed Exercise

    Standby Power Rating 130 kW STANDARD EQUIPMENT • All input connections in one single area • High coolant temperature shutdown • Low oil pressure shutdown • Low coolant level automatic shutdown • Low fuel pressure • Overspeed automatic shutdown • Adjustable cranking timer •...
  • Page 2: Generator Specifications

    APPLICATION & ENGINEERING DATA GENERATOR SPECIFICATIONS TYPE ...Synchronous ROTOR INSULATION ... Class H STATOR INSULATION ... Class H TOTAL HARMONIC DISTORTION ...<3.5% TELEPHONE INTERFERENCE FACTOR (TIF) ... <50 ALTERNATOR OUTPUT LEADS 3 PHASE ...4 wire BEARINGS...Sealed Ball COUPLING ...Gear Drive LOAD CAPACITY (STANDBY RATING) ...
  • Page 3 COMMERCIAL 130 kW OPERATING DATA KW RATING ENGINE SIZE GENERATOR OUTPUT VOLTAGE/KW - 60Hz 120/240V, single phase, 1.0 pf 120/208V, 3-phase, 0.8 pf 120/240V, 3-phase, 0.8 pf 277/480V, 3-phase, 0.8 pf GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% Single phase or 208V &...
  • Page 4 480 3 ø #6 to 350 mcm 600 3 ø #6 to 350 mcm www.guardiangenerators.com © 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. COMMERCIAL 130 kW COMMERCIAL SERIES NOTE: Door access...

This manual is also suitable for: