Manual Transfer And Startup; Engine Governor Adjustments - Generac Power Systems 005040-2 Owner's Manual

Liquid-cooled, prepackaged standby generator
Table of Contents

Advertisement

Condition
Ready (Green)
Generator Switch is
in the OFF Mode.
System Ready for
Automatic Start
Generator Switch is
in the MANUAL Mode
Weekly Exerciser
is not set
Battery Voltage <12V
for >1 minute
Battery Voltage <6V
Unit Shutdown due
to Low Oil Pressure
Unit Shutdown due
to High Temperature
Unit Shutdown due
to Engine Overspeed
Unit Failed to Start
during it's Crank Cycle
Utility Voltage is
<45% of Nominal
Engine Speed Signal Fault
Control Board is
in GTS Mode
3.2.6 SYSTEM READY LED
The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.
The system ready LED will be OFF when the switch
is in the manual or OFF positions.
The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.
This secondary function is only available with dip
switch two in the OFF position (ATS - automatic
transfer switch application).
14 Generac
®
Power Systems, Inc.
Section 3 - Operation
Guardian Liquid-cooled 25 kW Generator
System
Low
Bat (Red)
OFF
X
ON
X
OFF
X
X
Flashing
(-----------------------------------1 sec rate---------------------------------------)
X
ON
(Non-latching)
X
ON
OFF
X
OFF
X
OFF
X
OFF
X
Flashing
X
1 sec rate
OFF
X
OFF
X
X = indicates that the LED can be ON or OFF depending on the operating conditions.
Low
High
Oil (Red)
Temp (Red)
Speed (Red)
OFF
OFF
OFF
OFF
OFF
OFF
Flashing
Flashing
ON
ON
The five RED LED's will turn on one at a time
3.3
MANUAL TRANSFER AND
START-UP
To transfer electrical loads to the Standby (EMER-
GENCY) power source side and start the engine man-
ually, refer to the Owner's Manual of the particular
transfer switch.
3.4
ENGINE GOVERNOR
ADJUSTMENTS
Engine speed governing is also controlled by the
engine control board. The engine governor has been
set by the factory during final testing of the generator
and should not be adjusted.
If, however, adjustments are necessary, the following
procedure should be followed (Figure 3.2 and Section
3.8):
1. Move dip switch 8 to the test mode (OFF posi-
tion).
2. Set all three potentiometers (pots) fully counter-
clockwise.
Over
Over
Crank (Red)
OFF
OFF
OFF
OFF
OFF
OFF
Flashing
Flashing
ON
ON
Flashing
Switch Position
Manual
Auto
Off
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O