• The control board WILL monitor all engine condi-
tions and shut down on all the faults listed in this
document.
Pos2 OFF — Prepackaged ATS Application
• The control board will perform all of the automat-
ic features listed in this document.
• The two-wire start connections should NOT be
used.
GTS Mode Operation
When in GTS mode, the control board will respond
as follows based on the AUTO/OFF/MANUAL switch
position.
OFF — The generator will not start and run in this
position.
MANUAL — The control board will start and run the
generator whenever the switch is in the manual posi-
tion.
AUTO — The control board will monitor the two-wire
start circuit. When a two-wire start is sent, the con-
trol board will immediately start and run the genera-
tor. When the two-wire start is removed, the control
board will immediately stop the generator.
If the generator is installed in conjunction with an
engineered GTS type transfer switch, refer to the
applicable transfer switch manual for exact oper-
ating parameters and timing sequences.
3.2
CONTROL CONSOLE
COMPONENTS
The components of a home standby generator control
console (Figure 3.1) are as follows:
Figure 3.1 - Home Standby Generator Panel
LED INDICATORS:
FLASHING GREEN LED = NO UTILITY SENSE
5 FLASHING RED LED'S = EXERCISER NOT SET
(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON
RED LED'S = INDIVIDUAL FAULT
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)
4A
OFF
SET
ON
SET
EXERCISE
EXECISER
TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.
TIME
SWITCH
4A FUSE
BATTERY
CHARGER
NOTE:
OVER CRANK
RED LEDs
LOW BATTERY
SYSTEM READY
AUTO
OFF
MANUAL
GREEN LED
TO SET EXERCISER TIME
0E7194
AUTO/OFF/MANUAL
SWITCH
15A FUSE
MAIN
POWER
QUIETSOURCE™ 40kW Liquid-cooled Generators
3.2.1 AUTO/OFF/MANUAL SWITCH
Use this three-position switch as follows:
• Set the switch to AUTO for fully automatic opera-
tion. See "Automatic Operation" (Section 3.5).
• Set switch to MANUAL position to crank and start
the generator engine.
• Set switch to OFF position to shut down an oper-
ating engine. With OFF selected, operation will not
be possible.
With switch set to AUTO, engine can crank and
!
start suddenly without warning. Such automat-
ic start up normally occurs when utility source
voltage drops below a pre-set level. To prevent
possible injury that might be caused by such
sudden starts, set AUTO/OFF/MANUAL switch
to OFF before working on or around the unit.
Then, place a "DO NOT OPERATE" tag on con-
trol console.
3.2.2 FAULT INDICATOR LED
This LED goes ON when one or more of the following
engine faults occurs and when engine shuts down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/RPM Sensor Loss
• High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine pro-
tection functions.
3.2.3 15 AMP FUSE
This fuse protects the control console's DC control
circuit against electrical overload. If the fuse has
melted open because of an overload, engine cranking
and startup cannot occur. If the fuse needs to be
replaced, use only an identical 15-amp replacement
fuse. (Type AGC)
3.2.4 4.0 AMP INLINE FUSE
This fuse protects the battery charger against electri-
cal overload. If the fuse needs to be replaced, use only
an identical 4-amp replacement fuse (type AG).
This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.
3.2.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to
start and exercise automatically. "See Weekly
Exercise Cycle."
Section 3 - Operation
DANGER
NOTE:
Generac
®
Power Systems, Inc. 13