Removing Detector From Its Enclosure; Configuring The Detector Module; Wiring The Detector Module - Honeywell Fire Sentry SS4-AUV Installation Manual And Operating Manual

Ultraviolet (uv) digital electro-optical fire detectors stand-alone relay mode or 4-20 ma output option
Table of Contents

Advertisement

Model SS4-AUV/-AUV2 Ultraviolet (UV) Digital Electro-Optical Fire Detector
Installation Guide and Operating Manual
MAN0927_V3_1510-005_Rev H_06-13
2.2.2

Removing Detector from its Enclosure.

a. With electrical power off (verify that electrical power is off by making sure that the Detector's
LEDs do not blink for at least 15 seconds), loosen the Allen-head screw at the base of the
metal enclosure top lens cover.
b. Remove the cover and set it aside along with the "O" ring avoiding contamination.
c. Remove the three Philips head captive screws located on the top circuit board.
d. Carefully lift out the module, sliding it along the three metal standoffs.
2.2.3

Configuring the Detector Module.

Set the DIP switches located on the center PC board of the Detector module to the desired
settings. Refer to section 1.5 and Table 2 for DIP Switch settings

2.2.4 Wiring the Detector Module.

a. Insert the cables into the metal enclosure base through one of the conduit openings. Refer to
Figure 6
b. Connect the 24 Volt DC power supply wires to pins 1 (-) and 4 (+) of the J1 or J2 connector
observing the correct polarity. Refer to Figure 2. Firmly tighten down the two slotted screws
with a small screwdriver taking care not to over-tighten the screws.
Pins 2 and 3 of the J1 and J2 connectors are the RS-485 interface used only for downloading the
FirePic from the Detector's non-volatile memory, or for viewing the Tri-Mode Plot.
recommended to wire pins 2 and 3 to a separate junction box and properly identify them for future
use.
A color-coded, multi-connector, shielded, UL-rated cable with 18 to 24-gauge wire is
recommended for connecting to J1 or J2. The following color-coding is suggested as a guideline:
Verify
Relay
*Fault Relay
*Fault relay is shown in the energized condition during normal operation (No Fault)
Pin 1
Black
Green or Blue
DC R
( - )
RS-485( - )
ETURN
Figure 2: Bottom View of SS4-AUV/-AUV2 Detector Module
Pin 2
Pin 3
White or Yellow
RS-485( + )
It is
Pin 4
Red
+24 VDC P
( + )
OWER
7