Detector Pinout Data - Honeywell Fire Sentry SS4-AUV Installation Manual And Operating Manual

Ultraviolet (uv) digital electro-optical fire detectors stand-alone relay mode or 4-20 ma output option
Table of Contents

Advertisement

Model SS4-AUV/-AUV2 Ultraviolet (UV) Digital Electro-Optical Fire Detector
Installation Guide and Operating Manual
MAN0927_V3_1510-005_Rev H_06-13
TABLE 1: Stand-Alone Model SS4-AUV/-AUV2 Detector Connectors - Pinouts
J1: DETECTOR INPUT POWER
PIN
1
DC Return ( - )
2 and 3:
RS-485 Connection to an optional interface unit for viewing FirePic and TriMode Plot.
4
Power (+24 Volts DC)
J2: DETECTOR POWER OUT
PIN
1
DC Return ( - )
2 and 3:
RS-485 Connection to an optional interface unit for viewing FirePic and TriMode Plot.
4
Power (+24 Volts DC)
J4: FIRE RELAY
PIN
1
Fire Relay Common
2
Fire Relay Normally Closed
3
Fire Relay Common
4
Fire Relay Normally Open
J5:
FAULT RELAY (Energized)
PIN
1
Fault Relay Normally Open
2
Fault Relay Common
3
Fault Relay Normally Closed
4
Fault Relay Common

DETECTOR PINOUT DATA

J6:
PIN
1
2
3
4
FIRE VERIFY RELAY
Verify Relay Common
Verify Relay Normally Open
Verify Relay Common
Verify Relay Normally Closed
14