Table 34 Options Setup Parameters - Liebert ICOM User Manual

Intelligent communications & monitoring
Hide thumbs Also See for ICOM:
Table of Contents

Advertisement

Table 34
Options setup parameters
Function
Large Display
Page 1 of 2
Password
Compressor Sequence
Low Pressure Alarm Delay
Actual LP1 Pressure
Actual LP2 Pressure
Electric Stages
Hot Water Heat On/Off
Total Heat Stages
LWD Connected
3P Actuator Runtime
3P Actuator Direction
Page 2 of 2
Password
Humidification Enabled
Infrared Flush Rate
Dehumidification Enabled
Humidifier Bottle Flush Time
Humidifier Bottle Manual Flush
Single Unit Auto Restart
On-Off Enabled
CW Flush
Freecooling Flush
Hot Water Flush
Read/
Small Display
Write
PASSWORD
W
COMP SEQ
R
LP DELAY
W
LP1 ACT
R
LP2 ACT
R
EL HEAT
W
HW HEAT
W
ALL HEAT
R
LWDconn
W
3P RUN
W
3P DIR
W
PASSWORD
W
HUM ENAB
W
IR FLUSH
W
DEHUM EN
W
HumFlush
W
ManFlush
W
RESTART
W
ONOFF EN
W
CW FLUSH
W
FC FLUSH
W
HW FLUSH
W
69
Service Menu Parameters
Range
Default
Imperial (metric)
Setting
-
1, 2, auto
Auto
0-5 min
-145.0 - 725.0 psi
(-10.0 - 50.0 bar)
-145.0 - 725.0 psi
(-10.0 - 50.0 bar)
0, 1, 2, 3
No, Yes
No
0, 1, 2, 3
No, Yes
No
30-500 sec
165 sec
Direct, Reverse
Direct
-
No, Yes
Yes
110-500%
150%
No, Yes
Yes
5-30 sec
Yes, No
No
0-999 sec
Yes, No
Yes
0-99 hours
0-99 hours
0-99 hours
-
3
-
-
0
-
-
5
5
0
0
0