Table 8
Possible event settings—some events not available in all units
Event
MAIN FAN OVERLOAD
LOSS OF AIRFLOW
CLOGGED FILTERS
HIGH ROOM TEMP
LOW ROOM TEMP
HIGH ROOM HUM
LOW ROOM HUM
HIGH TEMP SENSOR A
LOW TEMP SENSOR A
HIGH HUM SENSOR A
LOW HUM SENSOR A
COMP 1 OVERLOAD
COMP 2 OVERLOAD
COMP 1 HIGH PRESSURE
COMP 2 HIGH PRESSURE
COMP 1 LOW PRESSURE
COMP 2 LOW PRESSURE
COMP 1 PUMPDOWN FAIL
COMP 2 PUMPDOWN FAIL
DIG SCROLL1 HIGH TEMP
DIG SCROLL2 HIGH TEMP
EL HEAT HIGH TEMP
WORKING HRS EXCEEDED
SMOKE DETECTED
WATER UNDER FLOOR
COND PUMP-HIGH WATER
LOSS OF FLOW
STBY GLYCOL PUMP ON
STANDBY UNIT ON
HUMIDIFIER PROBLEM
NO CONNECTION w/Unit1
UNIT X DISCONNECTED
LOSS OF POWER
CUSTOMER INPUT 1
CUSTOMER INPUT 2
CUSTOMER INPUT 3
CUSTOMER INPUT 4
CALL SERVICE
HIGH TEMPERATURE
LOSS OF AIR BLOWER 1
REHEAT LOCKOUT
HUMIDIFIER LOCKOUT
FC LOCKOUT
COMPRESSOR(S) LOCKOUT
COMP 1 SHORT CYCLE
COMP 2 SHORT CYCLE
Internal Delay
(Before Action Occurs)
2 seconds
3 seconds
2 seconds
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
1 Min After Fan On
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
Internal Calc.
5 Sec
0 Sec
2 Sec
2 Sec
2 Sec
5 Sec
Reset Delay: 10 Sec
2 Sec
2 Sec
2 Sec
Internal Calc.
Internal Calc.
0 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
0 Sec
0 Sec
34
Default Delay / Selectable
(Before Action Occurs)
5 seconds / 0 – 9999 *
3 seconds / 0 – 9999 *
2 seconds / 0 – 9999 *
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
30 seconds / 0 – 9999
no
no
no
no
no
no
no
no
no
no
0 sec / 0 – 9999
0 sec / 0 – 9999
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
-
-
No
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
2 sec / 0 – 9999 *
0 - 9999
0 - 9999
Operation
Type
(default)
ALM
ALM
WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
Fixed to WRN
ALM
ALM
ALM
ALM
ALM
ALM
ALM
ALM
ALM
ALM
WRN
Fixed to WRN
ALM
ALM
ALM
ALM
ALM
ALM
ALM
WRN
WRN
ALM
ALM
ALM
ALM
ALM
MSG
MSG
ALM
WRN
WRN
WRN
WRN
MSG
MSG