Standard Mode
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for
heating. SCR reheat output is adjusted proportionally as the Temperature Proportional Band varies
the requirement for heating from 0% to -100%. Compressors operate only when there is a call for cool-
ing as described in 3.2.2 - Compressor Control.
Figure 21 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.

Figure 21 Two single-step compressors with SCR reheat set to Standard mode

Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 0°F
66
-100%
Heating
67
68
69
0%
½ Proportional Band
SCR On
Cool 1
On
SCR
On
70
71
72
Cool 1 Off
Cool 2
SCR Off
Off
½ Proportional Band
Cooling 1 On
Cooling 2 On
25
Cool 2
On
73
74
100 %
Cooling
Operation