Honeywell • 26
Quick Setup
8.
Quick Setup
Frequency converter application
Choose Fieldbus (Bus/Comm) for the active control place (see Chapter 5.1).
Master software
1 = Write 100.0 1 to nviDrvSpeedStpt.
2 = Frequency converter status is RUN and output frequency is 1.00 * nviDrvSpeedScale.
3 = Write 0.0 0 to nviDrvSpeedStpt.
4 = Frequency converter status is STOP.
If nvoDrvStats bit 3 = 1 Status of frequency converter is FAULT.