Use; Information Menu - GE Digital Energy LP 11U Installation & User Manual

Ge power supply user manual
Hide thumbs Also See for Digital Energy LP 11U:
Table of Contents

Advertisement

g

5.3 Use

Once the unit is in operation, there is no need to switch the unit on/off during use.
If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7)
results in a total absence of the output voltage (also the bypass voltage) of at least 5 secs.
If an emergency shutdown switch has been installed (see 4.5.1.1-2, step 6) the UPS will stop immediately
when the switch is opened. Restart is only possible after closing the switch and turning the UPS off and on
again with the UPS on/off switch (rear panel, 7).
The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore
the UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.
The menus on the display can be divided into 5 groups:
1
standard screen
2

information menu (5.3.1)

3
status- and alarm menu (5.3.2)
4
service menu (5.3.3)
5
set-up menu (5.3.4)
The standard menu shows UPS model and actual load.
LP 5-11U
LOAD 37%
5.3.1 Information Menu
When the default screen is displayed the first information screen can be entered by depressing the 'up' key
(front panel, 4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information
screens. After the last information screen the default screen will appear.
The screens display the following information:
INPUT LINE
208V
2.45kW
60Hz
OUTPUT
208V
LOAD 50%
60.0Hz
°
BATTERY
23
C
271V
1.9A
AUTONOMY TIME
LEFT 5:27:00
OPERATING TIME
0YEAR
29DAYS
LX: OPM_LPU_11U_5K0_10K_1US_V030
Utility voltage and utility frequency, and the power delivered by the utility.
Output voltages and output frequency, and the power delivered by the UPS
(as % of the nominal UPS rating).
The temperature near the batteries, the battery voltage and the battery current
(charging: + value, discharging: - value).
The remaining battery runtime (or autonomy) during a utility failure.
The total operating time of the UPS.
25
Digital Energy
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)