GE Digital Energy LP 11U Installation & User Manual page 46

Ge power supply user manual
Hide thumbs Also See for Digital Energy LP 11U:
Table of Contents

Advertisement

g
Model
Heat dissipation
Linear load 240 Volt
100% load
LP-U
W
Btu/hr
W
5-11
571
1950
389
6-11
661
2254
381
8-11
948
3234
551
10-11
1090
3719
556
5-11/120 V
641
2187
425
6-11/120 V
744
2539
601
Model
Minimum free space required
(Inches)
front
side
LP-U
5-11
4
2
5-11 /120V
4
2
6-11
4
2
6-11 /120V
4
2
8-11
4
2
10-11
4
2
LP 5/6/8/10-11U installation drawings
Dimensions
Weight
50% load
h
w
d
Btu/hr
Inch
Inch
Inch
Lbs
1329
26.8
12.3
28.7
295
1300
26.8
12.3
28.7
295
1882
26.8
12.3
28.7
386
1896
26.8
12.3
28.7
410
1451
39.2
12.3
28.7
386
2051
39.2
12.3
28.7
386
Distance between mounting
Input overcurrent protection
holes (Inches)
(AMPS)
rear
x
y
z
120V
8
7.24
22.76
7.48
8
7.24
22.76
7.48
60
8
7.24
22.76
7.48
8
7.24
22.76
7.48
70
8
7.24
22.76
7.48
8
7.24
22.76
7.48
Air flow
Amb.
Rel.
Altitude
100%
temp.
humidity
(max 4000m)
load
non-cond.
m3/hr
°F
m
660
14-104
<95
<1000, derating
12.5% per 1000
660
14-104
<95
660
14-104
<95
660
14-104
<95
660
14-104
<95
660
14-104
<95
Output overcurrent protection (AMPS)
208V
240V
120V
120V
208V
(1 X)
(2X)
35
30
40
20
25
40
20
25
40
35
50
25
30
50
25
30
60
45
70
35
40
70
60
80
40
50
Digital Energy
Input wiring
utility volt.
utility volt.
utility volt.
output
120V
208V
240V
volt. 120V
2
2
2
AWG/mm
AWG/mm
AWG/mm
AWG/mm
N.A.
10/6
10/6
8/10
N.A.
8/10
10/6
8/10
N.A.
6/14
8/10
6/14
N.A.
4/22
6/14
4/22
6/14
N.A.
N.A.
8/10
4/22
N.A.
N.A.
8/10
240V
20
20
25
25
35
40
LP Series
Output wiring
output
output
volt. 208V
volt. 240V
2
2
2
AWG/mm
AWG/mm
10/6
10/6
10/6
10/6
8/10
8/10
8/10
8/10
10/6
10/6
10/6
10/6

Hide quick links: