UPS types
Corrects line voltage conditions as low as 70V and as high as 144V to within 2% of selected nominal voltage
Standard internal battery set offers 15 minutes runtime at half load (1250W) and 6 minutes at full load (2500W)
Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack
compatible) external battery packs
Compact rackmount form factor installs using only 2 rack spaces (2U) with a depth of only 26 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation
Optional 2-9USTAND accessory enables upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X.
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS
nominal voltage adjustment and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA L5-30P input plug / NEMA 5-15/20R & L5-30R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each
bank has 3 outlets)
Front panel LEDs offer current monitoring and battery charge level information
Network grade AC surge suppression
Field replaceable, hot swappable internal batteries and external battery packs
$250,000 Ultimate Lifetime Insurance

Specifications

OUTPUT
Output Volt Amp
Capacity (VA)
Output kVA capacity
(kVA)
Output Watt Capacity
(watts)
Output kW capacity
Output power factor
Output Capacity
Details
Crest Factor
Nominal Output
Voltage(s) Supported
Nominal Voltage
details
Frequency
compatibility
Frequency
compatibility details
Output voltage
regulation (line mode)
3000
3
2500
2.5
0.83
Max output is 3000VA 2400W at 100V, 110V, 115V nominal settings
3:1
100V; 110V; 115V; 120V; 127V
120V default
50 / 60 Hz
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start. Frequency conversion from 60
to 50 Hz -or- 50 to 60 Hz supported. Output capacity de-rates by 25% during frequency conversion operation.
+/- 2%