4-12. Positioning Jumper Links

3
1

4-13. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
Input Voltage (V)
Input Amperes (A) At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
OM-238 118 Page 20
.
A complete Parts List is available at www.MillerWelds.com
Tools Needed:
200 VOLTS
230 VOLTS
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
4
3/8 in.
2
153 980-D
Check input voltage available at
site.
1
Jumper Links Access Door
Open door.
2
Jumper Link Label
Check label − only one is on unit.
3
Input Voltage Jumper Links
Move jumper links to match input
voltage.
Close and secure access door.
153 980-D / 804 911-A
60 Hz Single
Phase
200
230
31
28
35
30
45
40
10
10
89
118
(27)
(36)
10
10